|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.13 - Governor,overspeed switch and seal
|
8.6.1.6.2
|
x
|
|
Governor sheave is worn down and needs to be replaced. Pull through is way too tight. Need to set safeties and spin governor on reinspection within 60 days.
|
10/10/2019
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.23 - Suspension rope
|
8.11.2.1.3(cc)(3) Replace when diameter is reduced (Re-Inspection)
|
x
|
|
Hoisting belts are rouged with steel strands poked through the belt. Belts shall be repaired/replaced. Maximum of 60 days to correct issue or unit will need to be red tagged out of service.
|
5/16/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power, annually.
|
9/22/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
|
|
Fire service must be tested and documented monthly. No Logs for 2022 - 2025.
|
9/22/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required shall be provided in the machine room. No MCP, repair/PM/Callback logs for 2022 - 2025.
|
9/22/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
9/22/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
|
|
Fire service must be tested and documented monthly. No Logs for 2022 - 2025.
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required shall be provided in the machine room. No MCP, repair/PM/Callback logs for 2022 - 2025.
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|