Inspection
Inspection Details
Equipment ID
18615
18615
Inspection Date
5/25/2023
5/25/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Thomas Jimas
Thomas Jimas
Relief Valve Pressure
660
660
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
19
19
External ID
a57803a2-94f3-4cb4-a39b-f17fdf76d7fb
a57803a2-94f3-4cb4-a39b-f17fdf76d7fb
Location
DM Realty
13321 N Outer 40 Rd, Town & Country, MO
Phone: (314) 786-1200
13321 N Outer 40 Rd, Town & Country, MO
Phone: (314) 786-1200
Owner
Attn: Carole Fitzgerald
DM Realty
13321 N Outer 40 Rd, Town & Country, MO 63017
Phone: (314) 786-1212
Email: Cfitzgerald@dunnandmiller.com
DM Realty
13321 N Outer 40 Rd, Town & Country, MO 63017
Phone: (314) 786-1212
Email: Cfitzgerald@dunnandmiller.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | 2) A light and outlet must be provided and shall be operational on the car top. The light must be guarded to prevent damage when accidentally hit by a person moving onto or around on the car top. The guard for light bulb has no screws in it and can be easily moved around, possibly causing damage to the bulb. | 10/14/2019 |
| conversion | conversion | n/a | No | No | 1) Emergency operation of signaling devices, lighting, communication and ventilation shall be maintained. The emergency battery seems to be weak causing the bell not to function properly when car 110 VAC is loss. The charging system appears to be not functioning properly. | 10/14/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | 1) The following documents specified in 8.6.1.2.2(a), (b), and (c) shall be written and permanently kept on-site in the machine room. Procedures for testing shall be keep on site. Ref: 8.6.1.2.2 | 7/29/2020 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | NFPA 10- 6.1.3.8.3 Installation Height 4" from floor | No | No | 2) Fire extinguisher shall be in a hanger per NFPA 13. Fire extinguisher will not fit in hanger safely in machine room. | 7/29/2020 |
| A17.1-2016 : Elevators | 5.11 - Plunger and Cylinder | 8.11.3.1.5(c) | No | No | 3) Oil leakage collected from each cylinder head seals or packing gland shall not exceed 19 L (5 gal) before removal. The container shall be covered and shall not be permitted to overflow. Lines from heads to tank shall be removed and replaced with containers. Ref: 8.6.5.5.2 | 7/29/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 10/29/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.5.7 Record of Oil Usage | No | No | A written record shall be kept of the quantity of hydraulic fluid added to the system and emptied from leakage collection containers and pans. Note: Per the State of Missouri: The use of oil recovery systems to return the hydraulic fluid back into the main reservoir by automatic means or by gravity feed prevents proper monitoring of the gland packing and seals. | 10/29/2021 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/21/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.7 Record of Oil Usage | No | No | A written record shall be kept of the quantity of hydraulic fluid added to the system and emptied from leakage collection containers and pans, shall not exceed 5 gal before removal, shall be covered, and shall not be permitted to overflow. | 9/21/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Per the State of Missouri AHJ: "The use of oil recovery systems to return the hydraulic fluid back into the main reservoir by automatic means or by gravity feed prevents proper monitoring of the gland packing and seals", and "machine rooms cannot be used as containment areas." | 9/21/2022 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | All cab lighting lamps shall work. | 9/16/2025 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Fire extinguisher shall be in the hanger per NFPA13. Fire extinguisher will not fit in the hanger safely in the machine room. | 9/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Adjust upthrust roller bearings for proper clearance to door hanger track. (2nd floor) | 9/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency phone fails to establish two-way communication. No dial tone at the controller. (Reinspect) |