Inspection
Inspection Details
Equipment ID
589
589
Inspection Date
6/19/2023
6/19/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Walter Tauchert
Walter Tauchert
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
37f7ea6b-ee9d-4b03-947b-3b80b1f86d9b
37f7ea6b-ee9d-4b03-947b-3b80b1f86d9b
Location
TandC OP LLC dba Town and Country Health & Rehab
13995 Clayton Rd, Town & Country, MO
Phone: (636) 227-5070
13995 Clayton Rd, Town & Country, MO
Phone: (636) 227-5070
Owner
Attn: Samuel Goldner Sole MBR
Samuel Goldner Sole MBR
525 Chestnut St, Ste 102, Cedarhurst, NY 11516
Phone: (000) 000-0000
Samuel Goldner Sole MBR
525 Chestnut St, Ste 102, Cedarhurst, NY 11516
Phone: (000) 000-0000
Billing
Attn: RayAnne Strubberg
TandC OP LLC dba Town and County Health & Rehab
13995 Clayton Rd, Town & Country, MO 63017
Phone: (636) 227-5070
Email: RayAnne.Strubberg@reachltc.com
TandC OP LLC dba Town and County Health & Rehab
13995 Clayton Rd, Town & Country, MO 63017
Phone: (636) 227-5070
Email: RayAnne.Strubberg@reachltc.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.2-211.8 | Yes | Yes | Phase 2 fire service shall be operational. (Estimated date of completion 3/26/2020) | 6/23/2020 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This unit is equipped with an overspeed valve that is due for a category 5 test. | 1/19/2022 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide a code compliant MCP including onsite documents. | 1/19/2022 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures and maintenance charts are missing. | 2/16/2023 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | The monthly fire service testing chart shall be maintained. | 2/16/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | 2/16/2023 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | No | Phase 2 fire service is not working | 6/19/2023 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Required documentation and MCP shall be kept in equipment room including wiring diagram, oil log, and fire service log recorded monthly. Fire service log is not being filled out. | 5/25/2023 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Pit shall be kept clean. Remove excess debris. | 5/25/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/25/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace unreadable key switch bezels in car and hall. | 5/25/2023 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Oil shall not be allowed to accumulate on the pit floor. The source of the leak shall be identified, corrected, and the oil shall be removed from the pit floor. | 2/4/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The fire service phase one key-switch bezel shall be legible. | 2/4/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The fire service phase two key-switch bezel shall be legible. | 2/4/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | No | 211.3c(2) - When the car is on Phase II fire service, and the Phase II switch is in the "HOLD" position, the elevator shall be on Phase II operation. The car shall remain at the landing with it's doors open. The door close buttons shall be inoperative. | 5/22/2025 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | No | No | The pit floor is covered in oil. The source of the leak shall be identified, corrected, and the oil shall be removed from the pit floor. | 2/4/2026 |