Inspection
Inspection Details
Equipment ID
16832
16832
Inspection Date
6/23/2023
6/23/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
19
19
External ID
d4c514ab-989c-4418-b18a-3a744e8a8804
d4c514ab-989c-4418-b18a-3a744e8a8804
Location
Cardinal Glennon Childrens Hospital
1465 S Grand Blvd, St. Louis, MO
Phone: (314) 577-5327
Alt Phone: (314) 678-5123
Fax: (314) 577-5314
Email: michael.jones3@ssmhealth.com
1465 S Grand Blvd, St. Louis, MO
Phone: (314) 577-5327
Alt Phone: (314) 678-5123
Fax: (314) 577-5314
Email: michael.jones3@ssmhealth.com
Owner
Attn: Madison Himelright
SSM Health- ESEP Department
1015 Corporate Square, Ste 160, St. Louis, MO 63132
Phone: (314) 577-5307
Email: madison.himelright@ssmhealth.com
SSM Health- ESEP Department
1015 Corporate Square, Ste 160, St. Louis, MO 63132
Phone: (314) 577-5307
Email: madison.himelright@ssmhealth.com
Billing
Attn: Mike Jones
SSM-Cardinal Glennon Childrens Hospital
1465 S Grand Blvd, St. Louis, MO 63104
Phone: (314) 577-5327
Alt Phone: (314) 678-5123
Fax: (314) 577-5314
Email: michael.jones3@ssmhealth.com
SSM-Cardinal Glennon Childrens Hospital
1465 S Grand Blvd, St. Louis, MO 63104
Phone: (314) 577-5327
Alt Phone: (314) 678-5123
Fax: (314) 577-5314
Email: michael.jones3@ssmhealth.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | The elevator hoisting ropes are showing a high degree of wear and shall be replaced. Replace ropes within 15 days of inspection. | 6/22/2018 |
| MO Minimum : Elevators | (A) - Hoistways | (A)6 | No | No | The gate switch on the elevator car door shall be adjusted so that when the door is in the closed position, the gap between the leading edge of the door and the strike jamb is no more than 2 inches. | 9/3/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. | 8/8/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | No | No | The top emergency exit has been impeded by electrical conduit added to the car for security cameras and cannot be opened. Remove conduit to allow escape hatch to be opened for maintenance and emergency personnel. | 10/20/2020 |
| A17.1-2016 : Elevators | 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) | 8.11.2.1.2(mm) | No | No | The seismic device on the counterweight did not initiate when activated. Repair device to operate when activated. | 10/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | A number of floors were missing the fire retaining tabs on the hoistway doors, install fire retaining tabs as required. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Full load test is incomplete, need to perform the following tests to complete inspection: drive machine brake with 125% of rated load, car safeties with rated load at rated speed, perform car buffer test at rated speed with rated load, counterweight buffer test at rated speed, test elevator for operation on emergency power, test phase I & II fire service. Re-inspection required | 7/28/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Elevator machine room air conditioner does not work, repair to keep equipment at correct operating temperature | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work on battery backup. Replace phone battery. Re-inspection required | 7/28/2025 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Suspension ropes are below minimum diameter, replace suspension ropes. Re-inspection required | 7/28/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | A number of floors were missing the fire retaining tabs on the hoistway doors, install fire retaining tabs as required. | 7/28/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test elevator for operation on emergency power, test phase I & II fire service. Re-inspection required | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | A number of floors were missing the fire retaining tabs on the hoistway doors, install fire retaining tabs as required. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work on battery backup. Replace phone battery. Re-inspection required | |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Suspension ropes are below minimum diameter, replace suspension ropes. Re-inspection required |