Inspection
Inspection Details
Equipment ID
13083
13083
Inspection Date
6/27/2023
6/27/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
500
500
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
20
20
External ID
87f1c4d0-93d8-4166-845a-9dd86ea0f3fd
87f1c4d0-93d8-4166-845a-9dd86ea0f3fd
Location
Friendly Temple Apartments Phase II
5521 WELLS AVE, SAINT LOUIS, MO
Phone: (314) 367-9700
5521 WELLS AVE, SAINT LOUIS, MO
Phone: (314) 367-9700
Owner
Attn: Executive Director, Joseph Hicks
Friendly Temple Apartments
5545 Wells Ave # 5521, St. Louis, MO 63112
Phone: (314) 867-8993
Email: jhicks@standrews1.com
Friendly Temple Apartments
5545 Wells Ave # 5521, St. Louis, MO 63112
Phone: (314) 867-8993
Email: jhicks@standrews1.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Empty drip pans, provide covers and remove oil from pit | 8/14/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Repair phone in car | 11/30/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Empty oil pans in pit and provide covers & remove oil from pit floor | 8/14/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Clean oil drip pans in pit and install covers | 8/14/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Clean oil drip pans in pit and install covers | 3/13/2025 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | Oversoeed valve past due for full load testing | 3/13/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service testing and document on log in machine room | 3/13/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 3/14/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 3/26/2025 |
| A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(5) Oil Leakage Collection | No | No | Empty drain pans. | 3/26/2025 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | No | No | Clean the pit. | 3/26/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | Provide existing battery backup lowering unit to work properly. | 3/26/2025 |