Inspection
Inspection Details
Equipment ID
136
136
Inspection Date
6/8/2023
6/8/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
Mitchell McNeely
Mitchell McNeely
Mechanic Name
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
b1306d35-6878-444b-98d7-35754e3cbffc
b1306d35-6878-444b-98d7-35754e3cbffc
Location
AUM Hospitality
9600 Natural Bridge Rd, St. Louis, MO
Phone: (314) 427-7600
9600 Natural Bridge Rd, St. Louis, MO
Phone: (314) 427-7600
Owner
Attn: Airport Inn St Louis Airport
Airport Inn St Louis Airport
2401 E Division St, National City, CA 91950
Phone: (000) 000-0000
Airport Inn St Louis Airport
2401 E Division St, National City, CA 91950
Phone: (000) 000-0000
Billing
Attn: Henry Hermes
Airport Inn St Louis Airport
9600 Natural Bridge Rd, St. Louis, MO 63134
Phone: (314) 798-0080
Email: henry.hermes@hotel-rl.com
Airport Inn St Louis Airport
9600 Natural Bridge Rd, St. Louis, MO 63134
Phone: (314) 798-0080
Email: henry.hermes@hotel-rl.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | x | Emergency phone shall work. | 5/22/2018 | |
| conversion | conversion | conversion - reinspect | x | Phone in cab still does not work | 11/6/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Current maintenance records to be kept in the machine room. | 4/29/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | Pit shall be kept clean and dry. | 4/29/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A copy of the MCP shall be kept in the machine room for each elevator | 2/19/2026 | ||
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | OSV is not sealed. Must be Cat 5 tested. Re-inspection required | 2/19/2026 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone line is not working when on emergency power, Re-inspection required | 11/30/2022 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Remove scavenger pump in elevator pit so oil loss can be monitored and logged in maintenance documents. | 2/19/2026 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Bell and Phone not Functioning (Red Tag) | x | x | Phone in elevator cab does not work on battery backup, needs repair. Red tagged, Re-inspection required | 6/8/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Bell and Phone not Functioning (Red Tag) | x | x | Alarm bell in elevator cab does not work, needs repair. Red tagged, Re-inspection required | 6/8/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | Elevator cab emergency lights do not work. Re-inspection required | 6/8/2023 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | A copy of the MCP shall be kept in the machine room for each unit | 2/19/2026 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | x | Phone failed to operate would not dial out. | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.19.15 Emergency Communications | x | x | Alarm bell failed to operate | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No current operating certificate. | |||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No MCP on-site | |||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | x | x | OSV due testing. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Remove scavanger pump from elevator pit, so oil loss can be monitored and logged in maintenance documents. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | A copy of the MCP shall be kept in the machine room for each unit. |