Inspection
Inspection Details
Equipment ID
18667
18667
Inspection Date
6/28/2023
6/28/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
22
22
External ID
92880c7d-2b4c-45c9-9047-8e7a0e446b97
92880c7d-2b4c-45c9-9047-8e7a0e446b97
Location
AmeriStar Casino
1 Ameristar Blvd, St. Charles, MO
Phone: (636) 940-4340
Alt Phone: (314) 809-9134
Email: Patmcdonald@boydgaming.com
1 Ameristar Blvd, St. Charles, MO
Phone: (636) 940-4340
Alt Phone: (314) 809-9134
Email: Patmcdonald@boydgaming.com
Owner
Attn: AmeriStar Casino- St. Charles LLC
AmeriStar Casino- St. Charles LLC
1260 S Main St, St. Charles, MO 63301
Phone: (000) 000-0000
Email: patmcdonald@boydgaming.com
AmeriStar Casino- St. Charles LLC
1260 S Main St, St. Charles, MO 63301
Phone: (000) 000-0000
Email: patmcdonald@boydgaming.com
Billing
Attn: Cardinal Elevator LLC
AmeriStar Casino- St. Charles LLC
2851 Barrett Station Rd., Ballwin, MO 63021
Phone: (000) 000-0000
Email: lisa@cardinalelevator.com
AmeriStar Casino- St. Charles LLC
2851 Barrett Station Rd., Ballwin, MO 63021
Phone: (000) 000-0000
Email: lisa@cardinalelevator.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on this elevator, elevator G4 was removed from service and complete inspection of this elevator could not be performed. Machine room and fireman’s service were only completed on this unit at this time, reinspection is required. | 2/14/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. | 7/27/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 2.18 | Yes | No | Upon pre-inspecting this governor for the required five year full load, the elevator safety governor was found to be worn to a degree that per the manufacturer specifications it shall be “replaced within 6 months”. Repair or replacement of the governor is required. This shall require an alteration permit, alteration inspection and a reinspection performed before the elevator will have a certificate of compliance issued. | 2/14/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on this elevator, the elevator was removed from service and complete inspection of this elevator could not be performed. The governor failed inspection and the safeties could not be set. A reinspection is required. | 4/10/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. | 8/9/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 2.18 | Yes | Yes | Upon performing the required five year full load, the elevator safety governor was found to be worn to a degree that the pull-through force was overly excessive and could potentially permanently damage the elevator safeties if testing proceeded. The elevator has been removed from service. Repair or replacement of the governor is required. This shall require an alteration permit, alteration inspection and a reinspection performed before the elevator will have a certificate of compliance issued. | 4/10/2023 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | No | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: The “call cancel” button is not labeled inside the car and shall be labeled correctly. | 4/10/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The emergency rescue battery in the controller has not been changed since 2019. The manufacture’s recommendation for replacement is 3 years. Replacement of the battery before the elevator shuts down due to battery being depleted is required. | 3/26/2024 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | There are a number of machine room lighting fixtures that are not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel. | 3/26/2024 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 102.4 | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. | 7/27/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Repair blower on hvac unit to provide proper temperature control for the machine room | 7/27/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Perform the required Cat 1 testing of the emergency generator | 2/10/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 6/15/2025 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 212 | Yes | No | The elevator hoisting belts are showing a high degree of wear and shall be replaced. Replace belts within 30 days of inspection. Reinspection is required. | 5/29/2026 |