Inspection
Inspection Details
Equipment ID
24267
24267
Inspection Date
6/30/2023
6/30/2023
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
James VanZant
James VanZant
Mechanic Name
Benjamin Kurzava
Benjamin Kurzava
Relief Valve Pressure
Slide
1in
1in
Governor Rope Pull
40/180
40/180
Door Closing Force
20
20
External ID
89f2853a-8949-41bd-8181-4c37ee3afa4b
89f2853a-8949-41bd-8181-4c37ee3afa4b
Location
MSSU-Nixon Hall
3950 Newman Rd, Joplin, MO
Phone: (417) 625-9301
3950 Newman Rd, Joplin, MO
Phone: (417) 625-9301
Owner
Attn: Greg Killingsworth
MO Southern State University
3950 Newman Rd, Joplin, MO 64801
Phone: (000) 000-0000
Email: PPInvoices@mssu.edu
MO Southern State University
3950 Newman Rd, Joplin, MO 64801
Phone: (000) 000-0000
Email: PPInvoices@mssu.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no certificate on site | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.11.2.1.1(e) Car Lighting | No | No | 8.11.2.1.1(e) (RD)one ceiling panel missing needs replaced | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | No | No | machine room door will not lock when door is shut | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | telephone will not call out | 7/26/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.4 Protection of Light Bulbs and Tubes | No | No | Cab lighting shall be guarded to prevent breakage. Ceiling panel missing, exposing glass lamps | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Machine Room Fire Extinguisher shall have current monthly/annual test tag. Expired | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | Machine room door shall be self-closing and self-locking. Door sticks. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.11.2.1.1(e) Car Lighting | Yes | No | Cab lighting shall be guarded to prevent breakage. Ceiling panel missing, exposing glass lamps(2020, 2021, 2022 Violation) | 6/30/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | Yes | No | Machine room door shall be self-closing and self-locking. Door sticks.(2020, 2021, 2022 Violation) | 6/30/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil loss log and Fire service testing log, recorded monthly. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 8.11.2.1.2(d) | No | No | Non-elevator related items shall not be stored in Machine Room. (Carpet Shampooer being stored in Equipment room) |