Inspection
Inspection Details
Equipment ID
10339
10339
Inspection Date
7/3/2023
7/3/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas Krug
Thomas Krug
Mechanic Name
David Schumer
David Schumer
Relief Valve Pressure
290
290
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
87041716-318a-45b5-a284-25275331881d
87041716-318a-45b5-a284-25275331881d
Location
Mercy Medical Office
15945 Clayton Rd, Ballwin, MO
Phone: (314) 581-1220
15945 Clayton Rd, Ballwin, MO
Phone: (314) 581-1220
Owner
Attn: Navvis Healthcare
Navvis Healthcare
15945 Clayton Rd, Ballwin, MO 63011
Phone: (000) 000-0000
Navvis Healthcare
15945 Clayton Rd, Ballwin, MO 63011
Phone: (000) 000-0000
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Replace backup battery on telephone in car | 10/2/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Telephone in car. Replace Backup Battery increase volume. | 6/16/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency Light and Bell do not work when normal power is removed (Reinspect) | 7/3/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | pits shall be kept clean of dirt and rubbish | 10/9/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Auxiliary Power fails to bring the car down and open the doors when normal power is removed. | 6/10/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Door Close and Door Open button do not work. | 10/9/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator. | 10/9/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Yes | No | Auxiliary Power fails to bring the car down and open the doors when normal power is removed. | 6/3/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace the slide guides that are missing on the top and bottom of the car | 10/9/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Provide Phase I Fire Service Instructions at main egress landing. The placard is missing | 10/9/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The Emergency Phone in the car fails to establish two-way communication. |