Inspection
Inspection Details
Equipment ID
2931
2931
Inspection Date
7/6/2023
7/6/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
James VanZant
James VanZant
Mechanic Name
Paul Bartlett
Paul Bartlett
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
23
23
External ID
56ba9bf4-a390-4d7f-8dcf-d3239b9bf681
56ba9bf4-a390-4d7f-8dcf-d3239b9bf681
Location
Sunvilla Towers
833 E ELM ST, SPRINGFIELD, MO
Phone: (417) 836-4725
833 E ELM ST, SPRINGFIELD, MO
Phone: (417) 836-4725
Owner
Attn: Work Management
Missouri State University
901 S National Ave, Springfield, MO 65897
Phone: (417) 836-8767
Email: workmanagement@missouristate.edu
Missouri State University
901 S National Ave, Springfield, MO 65897
Phone: (417) 836-8767
Email: workmanagement@missouristate.edu
Billing
Attn: Missouri State University
Missouri State University
901 S National Ave, Springfield, MO 65897
Phone: (417) 836-4904
Email: MPolm@MissouriState.edu
Missouri State University
901 S National Ave, Springfield, MO 65897
Phone: (417) 836-4904
Email: MPolm@MissouriState.edu
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | 2.4.2.1 suspension ropes need to be shortened | 10/22/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | telephone line is disconnected | 9/24/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | H(8). Multiple 4x4 electrical box in machine room needs to have wiring inside box and cover installed. | 10/22/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | 2019/2020 : 2-way communication device shall work and give proper location (REINSPECTION within 30 days) | 1/22/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)6 | No | No | H(6) Mainline disconnects, controllers, machines, and governors shall be numbered to correspond to each unit. | 10/22/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | 2019/2020 : 2-way communication device shall work and give proper location (REINSPECTION within 30 days) | 1/22/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine Room Fire Extinguisher shall have current monthly/annual test tag. Expired 2019 | 9/30/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Suspension rope shackles while have “anti-rotation”device installed, broken | 9/30/2021 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Hoist ropes has reduced diameter and shall be replaced within 30days. | 10/31/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | H(8). 4x4 electrical box in machine room needs to have wiring inside box and cover installed. ( phone connect box and Mach room lighting) | 9/6/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | 8.6.4.13 Adjust upthrusts for proper clearance (including but not limited to:8, 9,16,18) | 10/31/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Provide operational telephone in elevator cab | 7/6/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Provide operational pit light | 7/18/2023 |