Inspection
Inspection Details
Equipment ID
24945
24945
Inspection Date
6/21/2023
6/21/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Jeffrey Miller
Jeffrey Miller
Relief Valve Pressure
480
480
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
b73fa654-e609-4610-a31a-6139d110e1ae
b73fa654-e609-4610-a31a-6139d110e1ae
Location
Steelcoate Crossing
3419 Papin St, St. Louis, MO
Phone: (314) 496-3757
3419 Papin St, St. Louis, MO
Phone: (314) 496-3757
Owner
Attn: Leasing Office
Steelcoate Crossing
3419 Papin St, St. Louis, MO 63103
Phone: (314) 496-3757
Email: steelcote@2bresidential.com
Steelcoate Crossing
3419 Papin St, St. Louis, MO 63103
Phone: (314) 496-3757
Email: steelcote@2bresidential.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 8.11.2.1.3(p) | Yes | No | Close hoistway penetration, bevel ledges above the hoistway doors, and enclose walls at the top with rated drywall. | 7/8/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Enclose door frames in drywall, door frames are not free standing. | 7/8/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | Yes | No | Increase illumination in the control space to 19 ft candles minimum, measured from the floor. | 7/8/2020 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 | No | No | Replace missing lighting fixture in the pit. Light must be 19 foot candles in illumination | 1/10/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | No | No | Machine / control room space illumination is less than 19 fc. No lighting in hoistway control space at 2nd floor | 10/1/2022 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | Smoke detector head is missing on top landing. Replace/reinstall. Reinspection within 10 days. Only unit in building. Did not red tag at this time | 5/28/2024 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | No | No | machine/control room/space illumination is less than 19fc. no lighting in hoistway control space at 2nd floor | 1/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | No | No | Machine room illumination is less than 19 fc, no lighting in hoistway control space at 2nd floor | 1/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | No | No | Machine/ control room space illumination is less than 19 fc. No lighting in hoistway control space at 2nd floor. | 1/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car does not work, needs repaired. Re-inspection required | 1/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | No | No | Machine/ control room space illumination is less than 19 fc. No lighting in hoistway control space at 2nd floor. |