Inspection
Inspection Details
Equipment ID
12876
12876
Inspection Date
6/9/2023
6/9/2023
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
170/710
170/710
Door Closing Force
24
24
External ID
ae2f3f75-7849-4dfc-aea9-99716276d484
ae2f3f75-7849-4dfc-aea9-99716276d484
Location
City Place 1
1 Cityplace Dr, Creve Coeur, MO
Phone: (314) 787-1976
1 Cityplace Dr, Creve Coeur, MO
Phone: (314) 787-1976
Owner
Attn: RNSI City Place, LLC
RNSI City Place, LLC
2 Cityplace Dr, Ste 460, St. Louis, MO 63141
Phone: (314) 594-5013
Email: cityplace@redico.com
RNSI City Place, LLC
2 Cityplace Dr, Ste 460, St. Louis, MO 63141
Phone: (314) 594-5013
Email: cityplace@redico.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Replace missing hoistway door pick up rollors on 3rd and 4th floor | 2/9/2021 |
| MO Minimum : Elevators | (D) - Brakes | (D)2 | Yes | Yes | The drive machine brake will not hold position with an empty car at the upper landings. The elevator was placed out of service and a stop operation order issued. The brake shall be readjusted to hold a 125% capacity and a reinspection is required. | 6/14/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. | 6/14/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. | 6/14/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | 1. The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. | 6/22/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | 2. When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. | 6/22/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | Counterweight runby is "0". Shorten suspension ropes. Reinspect within 30 days. | 12/2/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be n display in the machine room | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car shall work on backup power. | 12/12/2023 |
| MO Minimum : Elevators | (D) - Brakes | (D)2 | Yes | Yes | Brake failed 125% test. Red Tagged, removed from service | 12/12/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Teh following test need to be performed to complete Cat. 5 inspection: full load, full speed safeties, car and counterweight buffers. retest 125% brake. | 12/12/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Place current state operationg certificate in elevator machine room. rule 40-5.100(2) | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car is not working. Re-inspection required | 2/1/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current operating certificate shall be displayed in the machine room | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The following tests need to be performed to complete Cat 5 inspection: full load, full speed safeties, can & counterweight buffers. Re-inspection required | 2/1/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car is not working on backup power. Re-inspection required | 6/4/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state certificate shall be displayed in the machine room | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work. Re-inspection required | 6/9/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Need to replace faulty light switch on cartop operating station | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room |