Inspection
Inspection Details
Equipment ID
18315
18315
Inspection Date
6/14/2023
6/14/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Phillip Moise, Jr.
Phillip Moise, Jr.
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
25
25
External ID
177e34bf-9376-495f-96dc-c37231826e72
177e34bf-9376-495f-96dc-c37231826e72
Location
Dickmann Building
3115 S GRAND BLVD, SAINT LOUIS, MO
Phone: (314) 932-1159
3115 S GRAND BLVD, SAINT LOUIS, MO
Phone: (314) 932-1159
Owner
Attn: GST Properties LLC
GST Properties LLC
3115 S Grand Blvd, Ste 300, St. Louis, MO 63118
Phone: (000) 000-0000
Email: mjghio@gmail.com
GST Properties LLC
3115 S Grand Blvd, Ste 300, St. Louis, MO 63118
Phone: (000) 000-0000
Email: mjghio@gmail.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Governor and safeties shall be tested. | 5/22/2020 |
| conversion | conversion | n/a | No | No | Need copy of current state operating certificate in machine room. | 6/13/2023 |
| conversion | conversion | n/a | No | No | Door closing force exceeds 30 lbs. | 6/13/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/13/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Remove all material, including 4 cinder blacks from the car top. | 6/13/2023 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Install a cover on the door operator. | 6/13/2023 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | No | Install a suspension rope and governor rope data tag. | 6/13/2023 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Remove unsupported wiring from the overhead. | 6/13/2023 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | The holes in the overhead shall be sealed with approved solid material. | 6/13/2023 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | The open electrical box with exposed wiring in the hoistway at the 4th floor shall be covered. | 6/13/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | The material not necessary for the operation of the elevator, trash, and defective parts shall be removed from the machine room. | 6/13/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | The covers shall be installed on all electrical equipment in the machine room, including the controllers. | 6/13/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)6 | No | No | The machines shall be numbered. | 6/13/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | A monthly fire service testing log shall be posted and kept on-site. | 6/13/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A maintenance control program (MCP) shall be provided. | 6/13/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams | No | No | An up to date, legible copy of the schematics shall be located in the machine room for each elevator. | 6/13/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)7 | No | No | Wiring running from controller 1 to controller 2 shall be enclosed in raceway or wireway. | 6/13/2023 |
| MO Minimum : Elevators | (J) - Counterweights | (J)2 | No | No | Suspension ropes on counterweight shackles shall have all cotter pins installed. | 6/13/2023 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Traveling cables shall be properly supported and run in wireway or raceway 6' past the point of suspension in the hoistway. | 6/13/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current ABC type fire extinguisher shall be located in the machine room. | 6/13/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | The safeties pulled out 60" for the annual test. The drum operated safety rope shall pull out a maximum of 42" before the safeties contact the rail | 3/3/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | The car top shall be kept clean. Clean the car top. | 6/13/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency bell shall be operational. | 3/28/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency lighting shall be operational. | 3/28/2024 |