Inspection
Inspection Details
Equipment ID
15042
15042
Inspection Date
6/26/2023
6/26/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
420
420
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
17
17
External ID
990cf8eb-5302-4dc3-a6b4-e466883bca15
990cf8eb-5302-4dc3-a6b4-e466883bca15
Location
Crestview Apartments
401 Ameristar Blvd, Bldg A, Building A ,St. Charles, MO
Phone: (000) 000-0000
401 Ameristar Blvd, Bldg A, Building A ,St. Charles, MO
Phone: (000) 000-0000
Owner
Attn: DeVault Management
DeVault Management
2000 Sherman Square Dr, St. Charles, MO 63303
Phone: (000) 000-0000
Email: devaultprop@aol.com
DeVault Management
2000 Sherman Square Dr, St. Charles, MO 63303
Phone: (000) 000-0000
Email: devaultprop@aol.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | No | No | Provide a code compliant fire extinguisher in the elevator machine room. | 10/24/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | No | No | Provide code compliant fire extinguisher in the machine room. | 10/24/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.7 Firefighters' Emergency Operation: Operating Procedures | No | No | Provide lobby warning placards on all elevator entrances. | 10/24/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide MCP. | 10/24/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | A fire service testing log shall be kept on-site. | 10/24/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.3 Guards Between Adjacent Pits | No | No | Clean the pit. | 10/24/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.3.1.2(c) | No | No | Provide code compliant machine room lighting (10fc). | 10/24/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.12 - Car enclosure | 8.11.2.1.1(l) | No | No | Tighten handrail in car, as needed. | 10/24/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | No | No | Clean the car top. | 10/24/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate. | 10/24/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/24/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Oil usage, findings for firefighters' service operation tests, and other records, along with instructions for locating such records shall be posted as required by A17.2, Item 2.41 | 8/24/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | A sign compliant with A17.1 2005 - Section 2.27.9 shall be posted adjacent to hall call fixtures instructing occupants not to use the elevator in case of fire. | 8/24/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.12 - Pipes, wiring, and ducts | 8.11.2.1.3(r) | No | No | All electrical wiring in the hoistway shall be enclosed in metal conduit, flexible conduit, metal raceway, or be in compliance with NFPA 70, National Electric Code. The unenclosed wiring near the second landing shall be enclosed. | 8/24/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 11/9/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Excessive debris must be cleaned out of pit. | 10/10/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | Battery lowering shall work. | 3/30/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation shall be provided in the machine room. Logs from 2022 - 2025 missing. | 3/19/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Fire service testing shall be documented monthly on log sheet. | 3/19/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | Machine room door shall be self-closing and self-locking. | 3/19/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit shall be kept clean. | 3/19/2026 |