Inspection
Inspection Details
Equipment ID
20209
20209
Inspection Date
5/31/2023
5/31/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Michael Beachner
Michael Beachner
Relief Valve Pressure
580
580
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
15F/16R
15F/16R
External ID
a82e119f-b36b-47d0-8644-ae456da4e91a
a82e119f-b36b-47d0-8644-ae456da4e91a
Location
Arrowhead Stadium
1 Arrowhead Dr, Kansas City, MO
Phone: (816) 921-3600
1 Arrowhead Dr, Kansas City, MO
Phone: (816) 921-3600
Owner
Attn: Jackson County Sports Authority
Jackson County Sports Authority
1 ARROWHEAD DR, KANSAS CITY, MO 64129
Phone: (816) 920-4962
Email: krutter@chiefs.nfl.com
Jackson County Sports Authority
1 ARROWHEAD DR, KANSAS CITY, MO 64129
Phone: (816) 920-4962
Email: krutter@chiefs.nfl.com
Billing
Attn: Jackson County Sports Authority
Jackson County Sports Authority
1 ARROWHEAD DR, KANSAS CITY, MO 64129
Phone: (816) 920-4962
Email: tidel@chiefs.nfl.com
Jackson County Sports Authority
1 ARROWHEAD DR, KANSAS CITY, MO 64129
Phone: (816) 920-4962
Email: tidel@chiefs.nfl.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | replace the emergency light battery, it is dead | 7/28/2025 | ||
| conversion | conversion | n/a | only allowed to have one three position phase 1 keyswitch, the phase 1 keyswitch at the lower alternate landing needs to be removed or replaced with a two position phase 1 keyswitch | 7/28/2025 | ||
| conversion | conversion | n/a | the front door open and door close buttons operate the rear doors and the rear door open and door close buttons operate the front doors both on the car operating panel and the fire service phase 2 panel | 7/28/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | x | x | remove the three-position key-operated switch at the alternate landing (the bottom landing) only allowed to have a three-position key-operated switch at the designated level (the top landing). there are currently three-positions switches at both landings. | 5/11/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | x | repair both the front and rear opening door restrictors, neither are working | 5/11/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.11.2.1.1(e) Car Lighting | replace the emergency light battery, it is dead | 7/28/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | x | x | in the fire service phase 2 operating panel the buttons marked front door open/close operates the rear door and the buttons marked rear door open/close operates the front door. Rewire the buttons to operate the correct openings doors as they are labeled | 5/11/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | x | x | Violation still remains - the operation of buttons on the fire service phase 2 panel is reversed. the buttons labeled front operate the rear door, and the buttons labeled rear operate the front door | 5/13/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | x | x | violation still remains - can not have two fire service phase 1 keyswitches that are 3 position. currently have 3 position keyswitches at both landings | 5/13/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | x | replace the emergency light battery, it is dead | 5/13/2021 | |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(c) | The Maintenance Control Program On-Site documents are not in the machine room. | 7/28/2025 | ||
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. | 7/28/2025 | ||
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.11.3.1.2(j) | Machine room fire extinguisher inspection tag is from 2019, it is to be inspected and tagged annually. | 7/28/2025 | ||
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the certificate in the machine room is from 2017 | 7/28/2025 | ||
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | A Maintenance Control Program (MCP) for each unit shall be provided by the person and/or firm maintaining the equipment and shall be viewable onsite by elevator personnel at all times. | 7/28/2025 | ||
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(c)(2) | A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room. | 7/28/2025 | ||
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | Did not have a written record of the maintenance performed on this elevator in the machine room. | 7/28/2025 | ||
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(c)(1) | did not have a record of oil usage in the machine room | 7/28/2025 | ||
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | emergency phone kept getting busy signal, reprogram phone to working number | 6/10/2022 | |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Car Emergency System (Re-Inspection) | x | the emergency light and bell did not work on the main car operating panel | 5/31/2023 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | emergency phone was not answered | 11/14/2023 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.27 - Crosshead data plate | 2.16.3 | does not have a crosshead data tag, provide a crosshead data tag | 7/28/2025 |