Inspection
Inspection Details
Equipment ID
20797
20797
Inspection Date
7/1/2024
7/1/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
18
18
External ID
bc46300f-3e93-47d7-b1e5-38a9a28fb47d
bc46300f-3e93-47d7-b1e5-38a9a28fb47d
Location
Chaminade College Prep School
425 S LINDBERGH BLVD, SAINT LOUIS, MO
Phone: (314) 993-4400
425 S LINDBERGH BLVD, SAINT LOUIS, MO
Phone: (314) 993-4400
Owner
Attn: Chaminade College Prep School
Chaminade College Prep School
425 S Lindbergh Blvd, St. Louis, MO 63131
Phone: (314) 993-4400
Email: mwingbermuehle@chaminade-stl.org
Chaminade College Prep School
425 S Lindbergh Blvd, St. Louis, MO 63131
Phone: (314) 993-4400
Email: mwingbermuehle@chaminade-stl.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Car emergency lighting shall work. | 9/5/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.11.2.1.1(e) Car Lighting | No | No | Emergency lights shall work. | 9/5/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Provide max counterweight sign in the pit. | 9/5/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 8/28/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | The emergency power jewel/indicator shall be operational to indicate unit has transferred to emergency power. Emergency power shall be tested and the emergency power jewel shall be operational. | 11/7/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency power operation not working. Generator would not transfer power. | 7/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 7/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | The in car emergency light shall be operational. | 7/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.24.8.4 Means for Manual Release | Yes | No | The manual brake release was not able to be tested. Testing procedures shall be kept on-site. | 7/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Fire stops are missing on both hoistway doors at 1st and 2nd floors. | 7/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 7/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | Yes | 2-way communication device shall work. Red Tag Issued, phone did not work on 7/5/23 inspection. | 8/21/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.24.8.4 Means for Manual Release | Yes | No | Emergency brake release handle shall work. | 8/21/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current state operating permit shall be obtained and displayed in the equipment room. | 8/21/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.24.8.4 Means for Manual Release | Yes | No | Emergency brake release handle shall work. Violation still remains as of 8/21/24. | 10/25/2024 |