Inspection
Inspection Details
Equipment ID
23165
23165
Inspection Date
5/23/2023
5/23/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Thomas Suedkamp
Thomas Suedkamp
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
25
25
External ID
861c12bd-0775-4fec-a865-a07bfc22fbde
861c12bd-0775-4fec-a865-a07bfc22fbde
Location
Beyond Housing Headquarters
6506 WRIGHT WAY, SAINT LOUIS, MO
Phone: (314) 376-5839 Ext: 000-000-0000
6506 WRIGHT WAY, SAINT LOUIS, MO
Phone: (314) 376-5839 Ext: 000-000-0000
Owner
Attn: 24:1 Community Land Trust
24:1 Community Land Trust
6506 Wright Way, St. Louis, MO 63121
Phone: (314) 376-5839
Email: mterrell@beyondhousing.org
24:1 Community Land Trust
6506 Wright Way, St. Louis, MO 63121
Phone: (314) 376-5839
Email: mterrell@beyondhousing.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Fire service stop switch shall be inoperative while in flight. | 3/18/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | No | No | Provide a current tested fire extinguisher in the elevator machine room. | 9/16/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.1.4(l) | Yes | Yes | The in car stop switch shall be bypassed during Phase 1 operation. | 8/29/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) Currently rescue plan is missing. | 7/9/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.1.2(o) | Yes | Yes | The emergency brake and main brake shall each individually hold 125% of the rated load. Both brakes were unable to hold the required load. Elevator Red Tagged. | 6/16/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post a current state operating certificate in the machine room. | 2/9/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. The maintenance/repair records and the monthly fire service checklist are missing. | 2/9/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | The emergency rescue device (R&R unit) shall be operational. | 5/23/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | Install the center hoistway door hangers at all floors. | 5/23/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | Install the hoistway door center fire gibs at all floors. | 5/23/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | There is no fire extinguisher in the machine room. An ABC type fire extinguisher with a current test tag shall be provided in the machine room. | 2/9/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 2/9/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Install the center hoistway door hangers at all floors. (2nd Notice) | 8/22/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Install the hoistway door center fire gibs at all floors. (2nd Notice) | 8/22/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | The emergency rescue device (R&R unit) shall be operational. (2nd Notice) | 8/22/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | The MCP is not filled out. A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 2/9/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | The emergency rescue device (R&R unit) shall be operational. (3rd Notice) | 8/25/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be displayed in the equipment room in a non-combustible frame. | 4/1/2026 |