Inspection
Inspection Details
Equipment ID
25501
25501
Inspection Date
6/13/2023
6/13/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
15
15
External ID
4ddef018-5bf4-489b-b576-8a38be9fcc03
4ddef018-5bf4-489b-b576-8a38be9fcc03
Location
3765 Lindell CDG
3765 Lindell Blvd, St. Louis, MO
Phone: (318) 420-7387
Email: matt.oneill@cardinalgroup.com
3765 Lindell Blvd, St. Louis, MO
Phone: (318) 420-7387
Email: matt.oneill@cardinalgroup.com
Owner
Attn: Matt O’Neal
3765 Lindell Oz LLC
3765 Lindell Blvd, St. Louis, MO 63108
Phone: (618) 420-7387
Email: matt.oneill@cardinalgroup.com
3765 Lindell Oz LLC
3765 Lindell Blvd, St. Louis, MO 63108
Phone: (618) 420-7387
Email: matt.oneill@cardinalgroup.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | Yes | No | Increase car top illumination to provide 19 ft candles at the car top when car is in machine space or control space. Re-inspection required | 7/22/2021 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | Yes | No | Increase illumination to 19 ft candles measured at the floor below the control panel at the top floor. Re-inspection required | 7/22/2021 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Yes | No | Fire extinguisher in control space lobby. Re-inspection required | 7/22/2021 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.8 | Yes | No | Provide a single non GFI receptacle for the sump pump. Per NFPA 70 (NEC) Re-inspection required | 7/22/2021 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | Yes | Yes | Need to test heat & smoke detectors Re-inspection required | 7/22/2021 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Test emergency phone. Line not installed at time of inspection | 7/22/2021 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(d)(1) | No | No | Evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. | |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2 On-Site Documentation | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 12/6/2022 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Emergency/standby power operation of the elevator shall be tested to complete the annual inspection. | 12/6/2022 |
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.6.1.5 | No | No | The code data plate required by A17.1 2016, Section 8.9, shall be provided in plain view, securely attached to each main line disconnect or controller, or the means to test. | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.5 Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car telephone shall be operational on main and auxiliary power. Note: The phone worked on normal power but couldn't be tested on auxiliary power - no access to means of test. | 6/13/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency/standby power operations shall operate as required by A17.2 item 1.17. Note: The elevator ran only on rescue operation, and would not run after returning to the bottom floor, which is not the floor of egress. The presence of an emergency power supply at the elevator controller could not be verified - no access to means to test. | 6/13/2023 |
| A17.1-2016 : Elevators | 1.4 - Sills and car floor | 2.11.11.1 | No | No | The 7th floor tile is loose at the hoistway door, creating a tripping hazard. | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. The line appears to be dead. | 8/27/2024 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | Machine space door at floor 7 shall be lockable. The lock is missing. | |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2 On-Site Documentation | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. It is currently blank and on the cartop. |