Inspection
Inspection Details
Equipment ID
18342
18342
Inspection Date
6/15/2023
6/15/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Walter Tauchert
Walter Tauchert
Relief Valve Pressure
360
360
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
14F/14R
14F/14R
External ID
d248f1c6-fed5-49f4-b144-b98e844fc0d0
d248f1c6-fed5-49f4-b144-b98e844fc0d0
Location
Express Scripts
1 Express Way, St. Louis, MO
Phone: (314) 996-0900
Alt Phone: (314) 591-1716
Email: LBrewer@express-scripts.com
1 Express Way, St. Louis, MO
Phone: (314) 996-0900
Alt Phone: (314) 591-1716
Email: LBrewer@express-scripts.com
Owner
Attn: Hope Scott, Sr. Facilities Manager
Express Scripts
1 Express Way, St. Louis, MO 63121
Phone: (314) 775-8308
Email: Hope.Scott@express-scripts.com
Express Scripts
1 Express Way, St. Louis, MO 63121
Phone: (314) 775-8308
Email: Hope.Scott@express-scripts.com
Billing
Attn: Ken Gerry, Chief Building Engineer
Express Scripts Inc
8455 University Place Dr, # 2, St. Louis, MO 63121
Phone: (314) 750-5843
Email: Ken.Gerry@express-scripts.com
Express Scripts Inc
8455 University Place Dr, # 2, St. Louis, MO 63121
Phone: (314) 750-5843
Email: Ken.Gerry@express-scripts.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 3.26.10 | No | No | Auxiliary power lowering device shall be operational. | 10/5/2020 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.11.3.1.5(a) | No | No | There is water and oil that has accumulated in the pit. Remove the oil and water from the pit and correct source of leaks. The pit shall be kept dry. | 8/14/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 3.26.10 | Yes | No | Auxiliary power lowering device is still not operational. Repair as needed. | 6/1/2021 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | Emergency/standby power operation of the elevator shall be tested to complete the annual inspection. | 4/26/2022 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Battery lowering device is not operating properly. | 4/1/2023 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Battery lowering device is not operating properly. Note: Display reads LODC | 7/8/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State Operating Certificate is required in the machine room. | 8/14/2026 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | The oil log and fire service log shall be recorded monthly. They are not being updated. | 8/14/2026 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 8/26/2024 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Battery lowering shall be operational. | 8/26/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Heat detector shall be within 24" of sprinkler head in the machine room. | 8/26/2024 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Battery lowering shall be operational. Note: Not corrected at time of 8/26/24 re-inspection. | 8/15/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Heat detector shall be within 24" of sprinkler head in the machine room. Note: Not corrected at time of 8/26/24 re-inspection. | 8/15/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Battery lowering shall be operational. (2nd Notice) | 8/14/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Heat detector shall be within 24" of sprinkler head in the machine room. (2nd Notice) | 8/14/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/14/2026 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Pit shall be kept clean and dry. |