Inspection
Inspection Details
Equipment ID
6174
6174
Inspection Date
7/12/2023
7/12/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
986bc221-01ae-4413-9cf8-de8ce1d62738
986bc221-01ae-4413-9cf8-de8ce1d62738
Location
Hoctor Building
1016 W Columbia St, Farmington, MO
Phone: (573) 218-6855
1016 W Columbia St, Farmington, MO
Phone: (573) 218-6855
Owner
Attn: SORTS
SORTS
1016 W Columbia St, Farmington, MO 63640
Phone: (000) 000-0000
SORTS
1016 W Columbia St, Farmington, MO 63640
Phone: (000) 000-0000
Billing
Attn: OA Facilities Mgt.-Interagency
OA Facilities Mgt.-Interagency
301 W High St, Rm 780, Jefferson City, MO 65101
Phone: (000) 000-0000
OA Facilities Mgt.-Interagency
301 W High St, Rm 780, Jefferson City, MO 65101
Phone: (000) 000-0000
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.3.5 | Yes | No | An emergency power test with 125% capacity shall be performed and witnessed. | 12/2/2020 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | Provide testing of Phase I operations, record results. | 7/12/2023 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | Provide testing of Phase II operations, record results. | 7/12/2023 |
| A17.1-2016 : Elevators | 1.8 - Door closing force | 8.6.4.19.8 | Yes | No | Check door force. | 7/12/2023 |
| A17.1-2016 : Elevators | 2.29 - Car and counterweight safeties | 8.6.4.20.1 | Yes | No | Provide Cat 1 testing of car safeties, check slide..Car stopped running. | 7/12/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work on backup power and be answered 24/7. Re-inspection required | 4/17/2025 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)2 | Yes | Yes | Top final limit switch was not actuated before counterweights compressed buffer. Red-tagged, Re-inspection required | 4/17/2025 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)2 | Yes | Yes | Bottom final limit switch activates just as car compresses buffer. Red-tagged, Re-inspection required | 4/17/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light in car shall work for more than 3 seconds. Re-inspection required | 4/17/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Inspection incomplete, elevator ceased operation during testing. Need to perform the following tests to complete inspection: all fire service, pit equipment and get slide measurement. Re-inspection required | 4/17/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light in car shall work for more than 3 seconds. Re-inspection required | 10/7/2025 |