Inspection
Inspection Details
Equipment ID
8186
8186
Inspection Date
6/16/2023
6/16/2023
Inspection Type
Other Inspection
Other Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Richard Toeniskoetter
Richard Toeniskoetter
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
630b3b1c-8a13-4d36-afb3-cea183ede48d
630b3b1c-8a13-4d36-afb3-cea183ede48d
Location
Urshan College Student Housing
900 Corporate Pkwy, Wentzville, MO
Phone: (314) 838-8858
900 Corporate Pkwy, Wentzville, MO
Phone: (314) 838-8858
Owner
Attn: Manny Macias
Urshan College Student Housing
900 Corporate Pkwy, Wentzville, MO 63385
Phone: (314) 838-8858
Urshan College Student Housing
900 Corporate Pkwy, Wentzville, MO 63385
Phone: (314) 838-8858
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | No | No | The car sill is not level with the newer floor, creating a tripping hazard. | 2/3/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | The cab lighting shall be guarded to prevent accidental breakage or contact. | 2/3/2020 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Coax cable and ground wire in the hoistway shall be removed. | 2/3/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The pit lighting shall be operational. | 2/3/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post the current state operating certificate. | 2/3/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room door shall be self-locking. | 2/3/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | A maintenance log shall be kept on site. | 2/3/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | A monthly log of fire service testing shall be kept on site. | 2/3/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | The muffler is leaking and shall be repaired or replaced. | 2/3/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Replace the Phase 1 & Phase 2 bezel in the car and hallway. | 2/3/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher in the elevator machine room is expired and shall be serviced or replaced with a current tested ABC type extinguisher. | 6/30/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | 6/30/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room shall be cleaned. | 6/30/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | The door re-opening device is not work as it should. Repair as needed. | 3/30/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11.1.4(a) Elevators Placed in Inactive Status | Yes | Yes | Elevator is not running and requires many repairs. Unit is being placed out of service, inactive status. Car landed, made inoperable and locked out. | 10/19/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Pipes conveying liquid, gas, or vapor that cross overhead of elevator equipment or come in close proximity of the equipment shall be guarded or guttered. The gas line running in close proximity to the elevator equipment in the machine room shall be guttered or guarded. | 1/4/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | The machine room shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key. The lock-set on the door is not self-locking | 1/4/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | Yes | No | Feeder locations for the main and lighting branch circuit shall be marked on the disconnects. | 1/4/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Per Wentzville Fire Marshall Chris Cuddihee, the designated floor for main firefighters service recall shall be changed to the bottom landing, and the secondary recall to the second landing. This will require moving the phase one key-switch, instructions, and visual alert to the bottom landing. The egress floor signage inside the car and on the door frames, and the telephone monitor visual, audible, and key-switch shall also be moved/changed to make the bottom landing the main floor of egress. After this work is complete, a re-inspection shall be performed and all the initiating devices re-tested. | 1/4/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working on battery back up. Take corrective action and re-test. | 11/6/2024 |