Inspection
Inspection Details
Equipment ID
8634
8634
Inspection Date
9/26/2017
9/26/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Harris
David Harris
Mechanic Name
Relief Valve Pressure
450
450
Slide
Governor Rope Pull
Door Closing Force
External ID
Location
Victoria Park Bldg B
2718 Forum Blvd, Columbia, MO
Phone: (573) 446-1775
2718 Forum Blvd, Columbia, MO
Phone: (573) 446-1775
Owner
Elliott, Thomas
2718 Forum Blvd, Ste 1, Columbia, MO 65203
2718 Forum Blvd, Ste 1, Columbia, MO 65203
Billing
Attn: Victoria Park Condo Owners
304 Russell Blvd, , MO 65203
304 Russell Blvd, , MO 65203
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | non elevator stuff stored in machine room, also blocking access to main line disconnect | 11/20/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Need "IN Case of Fire" signs by each Hall call button. | 12/1/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Non-elevator STUFF can not be stored in Elevator Equipment room | 12/1/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | No storage allowed in Elevator equipment room | 12/20/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | TKE needs to supply maintenance records | 12/20/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Need to have In Case of Fire signs by each Hall call button | 12/20/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Machine room needs to be reachable in a clear and unobstructed manner | 12/20/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machin rooms shall be provided with at least 10 foot candles of lighting | 12/20/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher in Elevator machine room not checked since 2019 | 12/20/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | No lights in machine room, need to install adequate lighting | 10/5/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | No lights in machine room, need to install adequate lighting | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | MUST HAVE CURRENT TEST TAG ON FIRE EXTINGUISHERS |