Inspection
Inspection Details
Equipment ID
10523
10523
Inspection Date
7/19/2023
7/19/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Bailey
Michael Bailey
Mechanic Name
Keith Tynes, Jr
Keith Tynes, Jr
Relief Valve Pressure
290
290
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
18
18
External ID
d1de9093-2224-4fdc-9992-f7f7736efd0b
d1de9093-2224-4fdc-9992-f7f7736efd0b
Location
Lafayette Apartments
3447 Lafayette Ave, St. Louis, MO
Phone: (314) 772-1687
3447 Lafayette Ave, St. Louis, MO
Phone: (314) 772-1687
Owner
Attn: St. Louis Housing Authority
St. Louis Housing Authority
3520 Page Blvd, St. Louis, MO 63106
Phone: (000) 000-0000
Email: mderienzo@habitat.com
St. Louis Housing Authority
3520 Page Blvd, St. Louis, MO 63106
Phone: (000) 000-0000
Email: mderienzo@habitat.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | No maintenance records. 8.6.14.1 | 9/8/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self closing & self locking. Lock shall not be made to be disabled | 2/28/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove debris from elevator pit | 2/28/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Cleaning of Hoistways and Pits - Accumulation of dirt & debris in door sills and on door equipment | 2/28/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire Extinguisher past expiration date | 2/28/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Repair loose handrail inside elevator at rear of cab | 2/28/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Phone failed to operate | 1/9/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Phone failed to operate. | 1/17/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone failed to operate. | 2/23/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | backup generator shall be tested | 8/20/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone line not working | 8/20/2024 |
| A17.1-2016 : Elevators | 1.1 - Door Reopening Device | 8.6.4.13.1(c) | Yes | No | Light sensor on the door edge does not work when an object obstructs the door path. | 2/3/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall be reprogramed, there is no address listed on this account. |