Inspection
Inspection Details
Equipment ID
10167
10167
Inspection Date
7/20/2023
7/20/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Elder
Michael Elder
Mechanic Name
Darren Banul
Darren Banul
Relief Valve Pressure
480
480
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
20
20
External ID
26a45ea2-85a3-451b-b48b-8706b9b40ee5
26a45ea2-85a3-451b-b48b-8706b9b40ee5
Location
Lange Middle School
2201 Smiley Ln, Columbia, MO
Phone: (573) 886-2243
2201 Smiley Ln, Columbia, MO
Phone: (573) 886-2243
Owner
Attn: Columbia Public Schools
Columbia Public Schools
5909 Paris Rd, Columbia, MO 65202
Phone: (573) 214-3774
Email: JJohnson@cpsk12.org
Columbia Public Schools
5909 Paris Rd, Columbia, MO 65202
Phone: (573) 214-3774
Email: JJohnson@cpsk12.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Fire extinguisher in elevator machine room and mechanical room by elevator not inspected since 2014 | 9/30/2020 |
| conversion | conversion | n/a | No | No | Phase I fire service operation plaquered needed by key switch | 9/30/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door must be self-locking | 7/12/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone calls wrong # | 6/30/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Sump hole needs non combustible cover | 7/12/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Emergency lowering batteries are bad. 2016 8.6.4.19.7 I believe but can't find mo min | 6/30/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher out of date | 7/12/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone needs location information for contact | 7/20/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door must be self-locking | 12/21/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone needs correct contact | 7/11/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door must be self-locking | 12/21/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | STANDBY POWER MUST BE MADE OPERABLE | 7/30/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | STANDBY POWER MUST BE MADE OPERABLE |