Inspection
Inspection Details
Equipment ID
19773
19773
Inspection Date
8/17/2023
8/17/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
5caa1794-745b-49b6-bc93-5255a09afee3
5caa1794-745b-49b6-bc93-5255a09afee3
Location
Hotelco WW MO LLC
2801 Fountain Pl, Wildwood, MO
Phone: (503) 669-9999
2801 Fountain Pl, Wildwood, MO
Phone: (503) 669-9999
Owner
Attn: The Wildwood Hotel
Hotelco WW MO LLC
2801 Fountain Pl, Wildwood, MO 63040
Phone: (503) 669-9999
Email: ap@hotelco.com
Hotelco WW MO LLC
2801 Fountain Pl, Wildwood, MO 63040
Phone: (503) 669-9999
Email: ap@hotelco.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency telephone has incorrect car number, repair as needed. | 4/10/2020 |
| A17.1-1996 : Elevators | 3.9 - Floor and emergency identification numbering | 211.9 | No | No | Provide elevator numbering inside the car. | 1/23/2023 |
| A17.1-1996 : Elevators | 1.16 - Rated load, platform area, and data plate | 1001.2(a)(16) | No | No | A capacity plate shall be provided in the car. | 1/23/2023 |
| A17.1-1996 : Elevators | 1.1 - Door Re-opening device | 1001.2(a)(1) | No | No | The COP door open button does not work and shall be repaired. | 1/23/2023 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Replace means to identify COP phase 2 fire service panel. *Note* - All signs and labels on car COP have been removed, determine if any other other labels or signs are missing and replace as needed, per manufacturer specifications. | 1/23/2023 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Clean the pit. The pit shall be kept clean and dry. | 1/23/2023 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | No | No | There is a hoistway door dust cover in the pit. Replace dust cover on appropriate floor. | 1/23/2023 |
| A17.1-1996 : Elevators | 3.9 - Floor and emergency identification numbering | 1001.2(c)(15) | No | No | The car top shall be properly numbered. | 1/23/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 12/13/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.2 - Stop switches | 8.11.3.1.1(b) (Re-Inspection) | Yes | No | The in car stop switch is damaged and shall be repair or replaced as needed. The stop switch shall be tested once repaired or replaced. | 4/25/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 7/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 4/25/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is still not working. (2nd Notice) | 4/25/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency phone shall be operational. (2nd Notice) | 8/17/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current state operating certificate shall be obtained and displayed in the machine room. | 7/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 12/10/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 2.1.1 | Yes | No | Top of hoistway has two spinkler heads and one heat detector. Each spinkler head requires a heat detector within 24 inches. |