Inspection
Inspection Details
Equipment ID
2700
2700
Inspection Date
6/20/2023
6/20/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Dismas Bustamante
Dismas Bustamante
Relief Valve Pressure
400
400
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
21
21
External ID
6e842d9d-848c-4a51-89a1-b05808c00fc3
6e842d9d-848c-4a51-89a1-b05808c00fc3
Location
Physics
4747 TROOST AVE, KANSAS CITY, MO
Phone: (816) 234-1363
4747 TROOST AVE, KANSAS CITY, MO
Phone: (816) 234-1363
Owner
Attn: Chauncy Kuhl
UMKC- Campus Facilities Mgmt
1011 E 51st St, Kansas City, MO 64110
Phone: (816) 235-1363
Email: kuhlc@umkc.edu
UMKC- Campus Facilities Mgmt
1011 E 51st St, Kansas City, MO 64110
Phone: (816) 235-1363
Email: kuhlc@umkc.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone, it automatically hangs up before able to talk to campus police | 6/3/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current copy of the state operating certificate in the machine room | |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Post monthly fire service test log in the machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide access to the complete MCP in the machine room according to 8.6 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine room fire extinguisher inspection tag expired | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 3.27 | Yes | Yes | The fire service phase 1 keyswitch would not reset the elevator and put is back into normal operation, had to reset the elevator from the controller. All other features of fire service worked. | 7/28/2021 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.11.3.1.1(e) | No | No | replace the emergency light battery, it is dead. | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency phone hangs up as soon as the campus police answer the phone, neither side has a chance to talk before it disconnects | 7/28/2021 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.11.3.1.2(j) | No | No | the machine room fire extinguisher was last tagged in 2015, have the fire extinguisher inspected and tagged annually | |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(c) | No | No | Maintenance Control Program on site documents are missing | |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the certificate on display is from 2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | machine room fire extinguisher inspection tag is expired, have extinguisher inspected and tagged annually | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Machine room fire extinguisher inspection tag is expired, have the fire extinguisher inspected and tagged | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Emergency lights did not come on, the alarm bell did work. repair emergency lights so they work | 8/30/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Update expired fire extinguisher |