Inspection
Inspection Details
Equipment ID
19086
19086
Inspection Date
7/21/2023
7/21/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Mitchell McNeely
Mitchell McNeely
Mechanic Name
Thomas Suedkamp
Thomas Suedkamp
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
23
23
External ID
b88bb8e2-b4f2-47a3-9512-d32f49225d50
b88bb8e2-b4f2-47a3-9512-d32f49225d50
Location
The Crescent
153 Carondelet Plz, Clayton, MO
Phone: (314) 727-3900
Email: Jvanmier@thecrescentcondo.com
153 Carondelet Plz, Clayton, MO
Phone: (314) 727-3900
Email: Jvanmier@thecrescentcondo.com
Owner
Attn: The Crescent Condominium
The Crescent Condominium
155 Carondelet Plz, Ste 100, Clayton, MO 63105
Phone: (000) 000-0000
The Crescent Condominium
155 Carondelet Plz, Ste 100, Clayton, MO 63105
Phone: (000) 000-0000
Billing
Attn: Community Property Mgmt
The Crescent Condominium
242 Old Sulphur Spring Rd, Manchester, MO 63021
Phone: (000) 000-0000
The Crescent Condominium
242 Old Sulphur Spring Rd, Manchester, MO 63021
Phone: (000) 000-0000
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | No | No | The machine room lighting has been changed to a motion type switch to activate. While this is an energy saving measure, it also is a safety/code concern. Without motion, the switch deactivates the lighting, thereby leaving maintenance personnel with no lighting. Remove motion type switch to a conventional on/off switch. | 8/10/2020 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 1001.2(b)(6) | No | No | A ventilation cooling fan located in the elevator controller has failed. The fan shall be replaced as the manufacturer’s design. | 8/10/2020 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 206.7 | Yes | No | Suspension ropes showning sign of rouging and being undersized. Re-inspection is required. | 4/8/2019 |
| A17.1-1996 : Elevators | 2.12 - Controller Wiring, Fuses, Grounding, Etc. | 102.1 | No | No | Machine room inspection would not operate as designed. Repair the machine room inspection function as designed. | 8/10/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide on-site maintenance control program. | |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | No | No | Clean the pit. | |
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 1001.2(a)(15) | No | No | Post Phase I signage near firefighter's switch. | |
| A17.1-1996 : Elevators | 3.2 - Car top light and outlet | 1001.2(c)(2) | No | No | NFPA car top outlet has open neutral, repair as needed. | |
| A17.1-1996 : Elevators | 4.5 - Access to Hoistway | 1001.2(d)(5) | No | No | Hoistway access switch on COP is not working. Repair as needed. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Category 5 testing needs to be completed, was only able to conduct annual portion of test | 7/26/2022 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 8.6.4.8 Machine Room and Machinery Space | No | No | Machine room shall not be used for storage | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Yes | No | Machine space stop switch needs repaired or replaced. Only service car in building, needs to be repaired in 10 days or less. Re-inspection required | 9/5/2024 |
| A17.1-1996 : Elevators | 4.5 - Access to Hoistway | 1001.2(d)(5) | No | No | Hoistway access switch at top landing is not working, needs repaired and test access operation. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room |