Inspection
Inspection Details
Equipment ID
757
757
Inspection Date
7/27/2023
7/27/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James VanZant
James VanZant
Mechanic Name
Matthew Trehal
Matthew Trehal
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
15
15
External ID
dd46d30f-fba6-4a96-b4a4-b730904762fe
dd46d30f-fba6-4a96-b4a4-b730904762fe
Location
Franciscan
620 W Scott St, Springfield, MO
Phone: (417) 869-5417
620 W Scott St, Springfield, MO
Phone: (417) 869-5417
Owner
Attn: Sherri Lile Franciscan Villa Community Manager
Sustainable Management Inc
620 W Scott St, Springfield, MO 65802
Phone: (417) 869-5417
Alt Phone: (417) 869-5510
Email: franciscanmanager@gmail.com
Sustainable Management Inc
620 W Scott St, Springfield, MO 65802
Phone: (417) 869-5417
Alt Phone: (417) 869-5510
Email: franciscanmanager@gmail.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | water in pit rusting springs and channels | 12/17/2019 | ||
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | telephone needs to be replaced | 10/22/2019 | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | needs current certificate posted on site | 12/17/2019 | ||
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | pit light not working | 12/17/2019 | ||
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | x | G(1)/8.6.4.15/1.5.1(b) : Emergency lighting shall work with power loss. (Reinspection required) | 10/5/2021 | |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | I(1)/106.1 Pit shall be kept dry. Remove rust from pit channels, repaint, repair water leak. 8" water in pit | 10/15/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | G(1)Emergency/auxiliary lighting shall work with power loss. (2020 & 2021 VIO) | 9/7/2022 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | x | Car Door restrictor shall work. | 9/7/2022 | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Pit shall be kept dry. 4” water in Pit, drain, remove rust from pit channels, repaint, repair water leak. (2020 & 2021 violation) | 10/15/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | G(1) CARTOP: Clean/remove debris and metal dust covers | 10/15/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | G(1) Adjust all upthrust roller bearings for proper clearance, currently as much as 0.125”. | 10/15/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Machine Room Fire Extinguisher shall have current monthly/annual test tag. Expired | 10/15/2024 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Machine room lighting needs to be repaired | 10/15/2024 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Machine room door shall be self-closing and self-locking (currently deadbolt, not self locking) | 10/15/2024 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | x | Machine room door needs to be self closing & self locking. Re-inspection required | 7/27/2023 | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Display current operating certificate in machine room | 10/24/2023 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Provide current state operating certificate in machine room | 8/27/2024 |