Inspection
Inspection Details
Equipment ID
7931
7931
Inspection Date
7/27/2023
7/27/2023
Inspection Type
Major Alteration
Major Alteration
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Jonathan Harrison
Jonathan Harrison
Relief Valve Pressure
W330/r460
W330/r460
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
20
20
External ID
2f94579b-0fe5-4552-a3bf-30c26bfb64b6
2f94579b-0fe5-4552-a3bf-30c26bfb64b6
Location
Parkway Towers Office Bldg
225 S Meramec Ave, Clayton, MO
Phone: (314) 880-7676
225 S Meramec Ave, Clayton, MO
Phone: (314) 880-7676
Owner
Attn: Property Manager
BMO-I Parkway Towers, LLC c/o Intelica CRE
11701 Borman Dr, St. Louis, MO 63146
Phone: (314) 270-5991
Email: sashcraft@intcre.com
BMO-I Parkway Towers, LLC c/o Intelica CRE
11701 Borman Dr, St. Louis, MO 63146
Phone: (314) 270-5991
Email: sashcraft@intcre.com
Billing
Attn: Property Manager
BMO-I Parkway Towers, LLC c/o Intelica CRE
11701 Borman Dr, St. Louis, MO 63146
Phone: (314) 270-5991
Email: ap@intcre.com
BMO-I Parkway Towers, LLC c/o Intelica CRE
11701 Borman Dr, St. Louis, MO 63146
Phone: (314) 270-5991
Email: ap@intcre.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | x | Restricted opening inoperative, repair. | 9/30/2019 | |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | x | No audible signal on Phase I return. | 1/30/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | x | Repair car door restrictor. | 1/30/2020 | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | x | Door restrictor works intermittently. Repair or replace. | 10/1/2020 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Provide pit bucket for oil collection. | 9/17/2020 | ||
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | x | Provide feeder location on main line disconnect (NEC620.51) | 7/31/2023 | |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | x | Provide feeder location on 110v. disconnect(NEC620.51). | 7/31/2023 | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.8 | x | Provide pit GFCI outlet to work properly (NEC620). | 7/31/2023 | |
| A17.1-2016 : Elevators | 2.6 - Ventilation | 2.7.9.2 | x | Provide existing climate control in the elevator machine room to work properly. | 7/31/2023 | |
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.7.1 | x | Seal all machine room wall and ceiling penetrations. | 7/31/2023 | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | x | Existing pipes over the elevator equipment are leaking repair as needed. | 7/31/2023 | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | x | Existing pipes to be covered to prevent future leaks/condensation from the elevator equipment. | 7/31/2023 | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | x | x | Provide Phase I emergency recall operations by Fire Alarm Initiating Devices (FAID) | 7/31/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | Clean car top | |||
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | Seal top of hoistway, water entering. |