Inspection
Inspection Details
Equipment ID
22295
22295
Inspection Date
7/3/2023
7/3/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Thomas Suedkamp
Thomas Suedkamp
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
23
23
External ID
6edb3220-a925-477d-a0ca-592ae910b71c
6edb3220-a925-477d-a0ca-592ae910b71c
Location
At Still Dental Clinic
1500 Park Ave, St. Louis, MO
Phone: (660) 626-2800
1500 Park Ave, St. Louis, MO
Phone: (660) 626-2800
Owner
Attn: Facilities
AT Still University of Health
800 W Jefferson St, Kirksville, MO 63501
Phone: (660) 626-2297
Fax: (660) 626-2929
Email: facilities@atsu.edu
AT Still University of Health
800 W Jefferson St, Kirksville, MO 63501
Phone: (660) 626-2297
Fax: (660) 626-2929
Email: facilities@atsu.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.40 - Maintenance Records | 2.26.1.4 Inspection Operation | 8.6.1.2 - Provide a maintenance control program. | 6/5/2018 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.2 - Car top light and outlet | 8.11.2.1.3(b) | Provide a working car top light. | 6/5/2018 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | Provide guards on bulbs in machine space. | 6/5/2018 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | x | Provide "Do not use in case of fire" signage on 3rd floor lobby. | 4/25/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Display current state operating certificate. | 5/28/2019 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 9/30/2021 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | x | Emergency/standby power operation of the elevator shall be tested. | 9/28/2021 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.6 - Governor-rope tension devices | 8.11.2.1.5(g) | Subsequent to the first stop of the car following the opening of the tail switch tension switch, the car shall remain inoperative until the switch is manually reset. | 9/30/2021 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 8.11.2.1.3(s) | The toe guards at the 2nd and 3rd landings shall be properly secured. | 9/30/2021 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The handset in the controller shall be capable of two way conversation with the car. | 9/28/2021 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The handset in the controller shall be capable of two way conversation with the car. | 10/14/2021 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone work properly. (Operator can not put on hold and must know location and which elevator). | 6/9/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.6.4.19.11 A17.1 2016 Ascending Overspeed Protection, Unintended Movement Devices, and Emg Brake | x | The electronic brake release battery is no good. Repair and retest. | 6/9/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | x | All hoistway doors are missing fire gibs. | 6/9/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | x | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 6/9/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone work properly. (Operator can not put on hold and must know location and which elevator). | 7/8/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.6.4.19.11 A17.1 2016 Ascending Overspeed Protection, Unintended Movement Devices, and Emg Brake | x | The electronic brake release battery is no good. Repair and retest. | 7/8/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | x | All hoistway doors are missing fire gibs. | 7/8/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 10/18/2023 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | The pit shall be kept clean. Clean the pit. | 10/18/2023 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.24.8.4 Means for Manual Release | x | The means to release the brake (EBR) shall be operational. | 10/18/2023 |