Inspection
Inspection Details
Equipment ID
22605
22605
Inspection Date
7/5/2023
7/5/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Thomas Jimas
Thomas Jimas
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
f3593d5a-ada0-4f4f-a3f9-f864fcf0a5dd
f3593d5a-ada0-4f4f-a3f9-f864fcf0a5dd
Location
Children's Specialty Care Center
13001 N Outer 40, St. Louis, MO
Phone: (314) 575-1691
13001 N Outer 40, St. Louis, MO
Phone: (314) 575-1691
Owner
Attn: Jennifer Thompson
BJC Healthcare c/o Cushman & Wakefield
8300 Eager Rd, Ste 600D, St. Louis, MO 63144
Phone: (314) 996-5346
Email: jennifer.l.thompson@cushwake.com
BJC Healthcare c/o Cushman & Wakefield
8300 Eager Rd, Ste 600D, St. Louis, MO 63144
Phone: (314) 996-5346
Email: jennifer.l.thompson@cushwake.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Oil usage, findings for firefighters' service operation tests, and other records, along with instructions for location such records shall be posted. | 6/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 3/11/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Emergency/standby power operation of the elevator shall be tested to complete the annual inspection. (Unable to transfer power on date of inspection) | 6/24/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 3/14/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | The fire service testing log is not being filled out. | 3/14/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/14/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency power shall be tested. | 6/1/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | The car door shall be restricted from opening when in the closed position anywhere outside the unlocking zone. | 6/1/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | Yes | No | The unit is equipped with emergency power, but the indicator jewel is not working. | 7/5/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | The car door shall be restricted from opening when in the closed position anywhere outside the unlocking zone. | 7/5/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/5/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | The emergency/standby power shall be tested. Emergency power is scheduled to be tested this evening. | 6/5/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | The presence of an overspeed valve has been confirmed, along with an installation date of 2015. The overspeed valve shall be scheduled for the category 5 test on or before the next annual inspection. | 6/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Replace missing upper secondary door retainers on hanger bracket on 3rd floor fast door. | 9/2/2025 |