Inspection
Inspection Details
Equipment ID
7091
7091
Inspection Date
4/16/2018
4/16/2018
Inspection Type
Reinspection
Reinspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
9a753258-50b6-4db5-af86-c3ac48e832b5
9a753258-50b6-4db5-af86-c3ac48e832b5
Location
Lou Fusz Nissan
925 N LINDBERGH BLVD, CREVE COEUR, MO
925 N LINDBERGH BLVD, CREVE COEUR, MO
Owner
Lou Fusz Automobile
925 N LINDBERGH BLVD, CREVE COEUR, MO 63141-5901
925 N LINDBERGH BLVD, CREVE COEUR, MO 63141-5901
Billing
Attn: Lou Fusz Automobile
925 N LINDBERGH BLVD, CREVE COEUR, MO 63141-5901
925 N LINDBERGH BLVD, CREVE COEUR, MO 63141-5901
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | conversion - reinspect | x | Slow down on fire recall from hall key sw. inoperative, repair | 4/16/2018 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Fire extinguisher in machine rom is expired. Replace or have serviced | |||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A copy of current state operating certificate needs to be properly displayed in machine room | |||
MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Lighting in machine room shall be at least 10 foot candles at floor in front of controller. Repair light fixtures to provide efficient lighting | |||
MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | All non elevator related wiring in machine room shall be enclosed in conduit/ ductwork, walled off or removed | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Fire extinguisher in machine room is expired, replace or have serviced | |||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A copy of the current operating certificate shall be displayed in the machine room | |||
MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Lighting in machine room shall be at least 10 foot candles st floor in front of controller, repair light fixture to provide sufficient lighting | |||
MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | All non elevator related wiring in machine room shall be enclosed in conduit / ductwork, walled off or removed | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency phone in car is not working. Re-inspection required | ||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A copy of the current state operating certificate shall be displayed in the machine room | |||
MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Lighting in machine room shall be at least 10 foot candles st floor in front of controller. Repair light fixture to provide sufficient lighting | |||
MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | All non elevator related wiring in machine room shall be enclosed in conduit ductwork, walled off or removed |