Inspection
Inspection Details
Equipment ID
8521
8521
Inspection Date
6/12/2023
6/12/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
14
14
External ID
8fdc7d04-f4e1-423f-bd92-eecc6cbfa076
8fdc7d04-f4e1-423f-bd92-eecc6cbfa076
Location
Stifel Bank Tower
8000 Maryland Ave, Clayton, MO
Phone: (314) 000-0000
8000 Maryland Ave, Clayton, MO
Phone: (314) 000-0000
Owner
Attn: Jack Sorrentino
Hoffmann International Commercial Real Estate
8000 Maryland Ave, Clayton, MO 63105
Phone: (314) 725-8333
Email: jsorrentino@hoffmanncre.com
Hoffmann International Commercial Real Estate
8000 Maryland Ave, Clayton, MO 63105
Phone: (314) 725-8333
Email: jsorrentino@hoffmanncre.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Need to perform brake, buffer, car & counterweight, safety slide and fireman's recall/operation testing. | 8/1/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | The MCP is missing the evacuation procedures. (This item is for notification purposes for future violation in 2022) | 7/30/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Fire service operation must be tested. | 6/12/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Top emergency exit shall be properly secured. The bolts are damaged. | 9/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Hoist ropes showing signs of flattening and reduction in diameter. Currently measures "go". Ropes should be replaced before next annual test and check driver for damaged grooves. | 9/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Hoist ropes have some flattening on them but still measure "go". Ropes should be monitored for further wear. | 9/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Traveling cable strain device under car is broken and needs replacement. | 9/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | MCP shall be current including fire service test log. | 9/26/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current state operating certificate shall be displayed in machine room in non-combustible frame. | 9/26/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency power operations shall be tested. | 10/23/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | No | Suspension ropes shall be shortened. | 9/1/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Machine room floors, machinery and conrtol spaces shall be kept free of water, dirt, rubbish, oil, and grease. | 9/1/2026 |