Inspection
Inspection Details
Equipment ID
15779
15779
Inspection Date
7/26/2023
7/26/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Bradley Rasnake
Bradley Rasnake
Mechanic Name
Adam Schnurbusch
Adam Schnurbusch
Relief Valve Pressure
480
480
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
17
17
External ID
2c5c04ad-4d58-44e0-acb0-dc5bfb3b4505
2c5c04ad-4d58-44e0-acb0-dc5bfb3b4505
Location
Lambert St. Louis Int'l Airport
Lambert Field, St. Louis, MO
Phone: (314) 890-1331
Lambert Field, St. Louis, MO
Phone: (314) 890-1331
Owner
Attn: Construction & Maintenance Manager
St. Louis Lambert International Airport
10701 Lambert International Blvd, St. Louis, MO 63145
Phone: (314) 890-1331
Email: AirportAccountsPayable@flystl.com
St. Louis Lambert International Airport
10701 Lambert International Blvd, St. Louis, MO 63145
Phone: (314) 890-1331
Email: AirportAccountsPayable@flystl.com
Billing
Attn: Construction & Maintenance Manager
St. Louis Lambert International Airport
PO Box 10212, St. Louis, MO 63145
Phone: (314) 890-1331
Email: AirportAccountsPayable@flystl.com
St. Louis Lambert International Airport
PO Box 10212, St. Louis, MO 63145
Phone: (314) 890-1331
Email: AirportAccountsPayable@flystl.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Fire service call cancel button shall be labeled. | 11/8/2019 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Shall have proper access to car operating panel for maintenance and repairs. Current flooring does not allow panel to open. | 7/29/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 4/16/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 4/16/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 4/16/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 4/16/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency/standby power operation of the elevator shall be tested to complete the annual inspection. | 9/9/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | The wiring in the machine room shall be enclosed and electrical box covers shall be in place. | 7/27/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | No | No | Portions of the bottom of the car platform have rusted away and shall be repaired or replaced. Note: This is a plywood platform with a bottom liner of sheet metal. Large portions of the sheet metal are no longer there. This has a negative impact on the fire resistive integrity, and possibly the structural integrity of the platform. | 7/27/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | A leak in the hydraulic system occurred near the completion of testing. The source of the leak shall be identified and corrected. | 7/26/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Due to the leak in the hydraulic system, the following testing items still remain: The auxiliary power lowering operation shall be tested. | 7/26/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Due to the leak in the hydraulic system, the following testing items still remain: The over-speed valve shall be tested with rated load. | 7/26/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Due to the leak in the hydraulic system, the following testing items still remain: Fire service operation shall be tested. | 7/26/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Due to the leak in the hydraulic system, the following testing items still remain: Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 7/26/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency Generator testing needs to be performed. Re-inspection required | 9/15/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency power operation shall be tested. | 4/3/2026 |