Inspection
Inspection Details
Equipment ID
2124
2124
Inspection Date
7/26/2023
7/26/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Jerry Reasoner
Jerry Reasoner
Relief Valve Pressure
410
410
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
24
24
External ID
672039e3-6ad0-4e10-98af-2c6d6f71f608
672039e3-6ad0-4e10-98af-2c6d6f71f608
Location
Conception Abbey
37174 State Hwy VV, Conception, MO
Phone: (660) 944-3100
37174 State Hwy VV, Conception, MO
Phone: (660) 944-3100
Owner
Attn: Mark Wiederholt
Conception Abbey
37174 State Hwy VV, Conception, MO 64433
Phone: (660) 944-2968
Email: markw@conception.edu
Conception Abbey
37174 State Hwy VV, Conception, MO 64433
Phone: (660) 944-2968
Email: markw@conception.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light does not illuminate. | 7/31/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Cylinder drain lines need to removed from tank. Cylinder drain lines need to drain into seperate pit containers that are covered and no more than 5 gallon capacity. | 3/23/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light does not illuminate. Need to provide pit lighting. | 3/23/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | Test and log firefighter operation monthly | 9/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Cylinder drain lines run back to storage tank. Remove from storage tank and install in pit collection containers | 9/16/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Install covers on 4x4 junction boxes located on hoistway wall. | 9/16/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light does not illuminate. No electrical power at light fixture. Need to provide power to pit light fixture. | 9/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Cylinder drain lines shall be ran to pit collection container and not the hydraulic storage tank in the machine roo.. | 9/16/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light does not illuminate. No power at light fixture. Circuit breaker or wiring issue. | 9/16/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | Yes | No | ADJUST DOOR RESTRICTOR SO IT WORKS | 7/8/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | REPLACE SUMP PUMP COVER ( IT IS IN THE PIT) | 9/16/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | REMOVE STANDING OIL FROM PIT | 9/16/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | No | No | REDUCE THE CLOSING FORCE TO <30 LBS | 9/16/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | CLEAN OIL FROM PIT FLOOR AND REPAIR LEAK | 9/16/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | INSTALL SUMP COVER | 9/16/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | INSTALL A SELF CLOSER ON MACHINE ROOM DOOR |