Inspection
Inspection Details
Equipment ID
14589
14589
Inspection Date
9/5/2018
9/5/2018
Inspection Type
Reinspection
Reinspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Relief Valve Pressure
N/A
N/A
Slide
Governor Rope Pull
Door Closing Force
N/A
N/A
External ID
726fd286-723d-49a1-b084-c36fa0dd936a
726fd286-723d-49a1-b084-c36fa0dd936a
Location
Mesnier Elementary School
6930 WEBER RD, AFFTON, MO
6930 WEBER RD, AFFTON, MO
Owner
Affton School District
8701 MACKENZIE RD, AFFTON, MO 63123-3436
8701 MACKENZIE RD, AFFTON, MO 63123-3436
Billing
Attn: Affton School District
8701 MACKENZIE RD, AFFTON, MO 63123-3436
8701 MACKENZIE RD, AFFTON, MO 63123-3436
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Provide existing emergency lights to work | 7/13/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | In cab alarm bell shall work. | 9/5/2018 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | The fire extinguisher in the elevator machine room is expired and shall be replaced or serviced. | 7/13/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 10/19/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency phone dials and then hangs up. The in car emergency telephone shall operate per code. | 8/16/2023 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | The overspeed valve was last tested in 2017. It shall be tested with the rated load on or before the next annual inspection. | 8/16/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | There is no state operating certificate in the machine room. | 10/19/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 11/4/2024 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Battery lowering does not work. | 11/4/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Overspeed Valve tag is not updated. | 8/22/2024 |