Inspection
Inspection Details
Equipment ID
13470
13470
Inspection Date
8/2/2023
8/2/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
15
15
External ID
ae6e269c-bf2e-4479-9835-0657d7e65b17
ae6e269c-bf2e-4479-9835-0657d7e65b17
Location
Hanley Cooperation Tower
101 S Hanley Rd, Clayton, MO
Phone: (314) 655-5874
101 S Hanley Rd, Clayton, MO
Phone: (314) 655-5874
Owner
Attn: Harrison Decker
Hanley Corporate Tower
101 S Hanley Rd, Ste 1130, Clayton, MO 63105
Phone: (314) 269-1863
Email: HDecker@LPC.com
Hanley Corporate Tower
101 S Hanley Rd, Ste 1130, Clayton, MO 63105
Phone: (314) 269-1863
Email: HDecker@LPC.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (J) - Counterweights | (J)3 | Shackles on counterweights rubbing frame thin, need longer shackles. | 12/5/2019 | ||
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | x | Emergency lights in car not working | 11/27/2019 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Need maintenance control program on site posted on controller | 2/12/2021 | ||
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Counterweight governor rope has to be replaced, severe rouge and multiple strands broken | 1/18/2021 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | Need to include testing procedures in MCP on or before January 1,2022 | 9/17/2021 | ||
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Perform monthly fire service testing and document on log in machine room | 10/23/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Repair/replace deflector sheave within 60 days | 10/23/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | Provide testing procedures in the maintenance control program | 10/23/2024 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Clean pit | 10/23/2024 | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Complete annul test within 14 days unintended motion alternate fire designated floor | 7/21/2022 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | x | Replace/Repair deflector sheave top of hoistway | 9/18/2024 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.2 Replacement of Suspension Means (Re-Inspection) | x | Replace hoist ropes (red rouge & reduced diameter) | 9/18/2024 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Complete 5 yr test (Fire Service) Reinspection required | 11/4/2024 | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | Test emergency generator. Reinspection required within 30 days | 11/4/2024 | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | test emergency generator | 2/8/2025 |