Inspection
Inspection Details
Equipment ID
13156
13156
Inspection Date
6/21/2023
6/21/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
John Osowski
John Osowski
Relief Valve Pressure
420
420
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
9
9
External ID
863fa910-1f5c-4692-af74-866a607683b4
863fa910-1f5c-4692-af74-866a607683b4
Location
Jackson County Family Courts
625 E 26th St, Kansas City, MO
Phone: (000) 000-0000
625 E 26th St, Kansas City, MO
Phone: (000) 000-0000
Owner
Attn: Jackson County Family Courts
Jackson County Family Courts
625 E 26th St, Kansas City, MO 64108
Phone: (000) 000-0000
Email: Accountspayable@courts.mo.gov
Jackson County Family Courts
625 E 26th St, Kansas City, MO 64108
Phone: (000) 000-0000
Email: Accountspayable@courts.mo.gov
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | the alarm bell did not work on battery power | 7/12/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | the emergency phone did not work, no dial tone | 7/12/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | open egg crate ceiling panels, light tubes shall be guarded | 6/12/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | do not store non-elevator related material in the machine room | 6/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | the top direction limit was not activated during the stop ring test, | 6/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | car top work light bulb was missing | 6/12/2026 |
| MO Minimum : Elevators | (K) - Car Platforms and Car Slings | (K)4 | No | No | does not have a crosshead data tag | 6/12/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | elevator has an open egg crate drop ceiling, the light tube shall be guarded against breakage | 6/12/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection) | Yes | No | Repair the fire service and test all smoke and heat initiating devices. The Flashing hat was not working. | 9/29/2022 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency phone is not working. | 9/29/2022 |
| A17.1-2016 : Elevators | 4.5 - Access to Hoistway | 2.12.7 | Yes | No | The hoistway access, on the top level, is out of the lowering range. | 9/29/2022 |
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.9 | Yes | No | Provide a code data plate that reflects the new inspection code. | 9/29/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | does not have a crosshead data tag, provide crosshead data tag | 6/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | the emergency lights go out as soon as the alarm button is pressed and do not come back on, repair emergency light system | 6/5/2024 |
| A17.1-2016 : Elevators | 10.1 - Machinery space access, lighting, receptacle, and condition | 8.6.8.15.1 | No | No | ONLY ELEVATOR RELATED EQUIPMENT ALLOWED IN MACHINE ROOM | 6/12/2026 |