Inspection
Inspection Details
Equipment ID
14968
14968
Inspection Date
6/21/2023
6/21/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
John Osowski
John Osowski
Relief Valve Pressure
440
440
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
10
10
External ID
9ea4eef6-a669-4fac-a736-965be355a469
9ea4eef6-a669-4fac-a736-965be355a469
Location
Jackson County Family Courts
625 E 26th St, Kansas City, MO
Phone: (000) 000-0000
625 E 26th St, Kansas City, MO
Phone: (000) 000-0000
Owner
Attn: Jackson County Family Courts
Jackson County Family Courts
625 E 26th St, Kansas City, MO 64108
Phone: (000) 000-0000
Email: Accountspayable@courts.mo.gov
Jackson County Family Courts
625 E 26th St, Kansas City, MO 64108
Phone: (000) 000-0000
Email: Accountspayable@courts.mo.gov
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | do not store non-elevator related material in the machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | the alarm bell did not work on battery power | 7/12/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | the emergency phone did not work, no dial tone | 7/12/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | open egg crate ceiling panels, the light tubes shall be guarded | |
| MO Minimum : Elevators | (K) - Car Platforms and Car Slings | (K)4 | No | No | does not have crosshead data tag | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)6 | No | No | the hydraulic tank is not marked #4 | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | do not store non elevator related material in the machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | the emergency lights did not come on, the alarm bell worked | 8/17/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency phone did not work | 8/17/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | the pit bucket was overflowing in the pit | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | clean up oil and water mixture on the pit floor | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | elevator has an open egg crate drop ceiling panels, light tubes shall be guarded to prevent breakage | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | emergency lights and bell did not work, replace battery so that the emergency lights and bell work when the 110 volt power is off. | 6/21/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone says that it doesn't have emergency number programmed | 6/21/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | No | No | escape hatch is not secured from opening from inside the elevator | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | adjust the door restrictor, the hook did not catch | 6/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | does not have a crosshead data tag, provide a crosshead data tag | |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | No | No | the fire service phase 1 audible signal in the car operating panel did not work | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | the emergency light battery is dead, replace the emergency light battery | 6/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone has not been programmed with the phone number to call, program the emergency phone | 6/5/2024 |