Inspection
Inspection Details
Equipment ID
5519
5519
Inspection Date
10/9/2018
10/9/2018
Inspection Type
Reinspection
Reinspection
Inspector Name
Gerald Glynn
Gerald Glynn
Mechanic Name
Relief Valve Pressure
350
350
Slide
Governor Rope Pull
Door Closing Force
19
19
External ID
1b1e753e-2a25-4aa4-9542-1adf4bc89527
1b1e753e-2a25-4aa4-9542-1adf4bc89527
Location
Murphy Manor
128 WALL ST, JOPLIN, MO
128 WALL ST, JOPLIN, MO
Owner
Joplin Housing Authority
1834 W 24TH ST, JOPLIN, MO 64804-1511
1834 W 24TH ST, JOPLIN, MO 64804-1511
Billing
Attn: Joplin Housing Authority
1834 W 24TH ST, JOPLIN, MO 64804-1511
1834 W 24TH ST, JOPLIN, MO 64804-1511
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | Yes | No | 1.18 door restrictor needs repaired | 10/9/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | 8.6.4.13.1(l) door restrictor needs repaired | 10/7/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2.1 Phase 1 Emergency Recall OperationBy Fire Alarm initiating Devices | Yes | Yes | temporary under construction | 10/20/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | Car Door restrictor shall work. (less than 4" opening) (REINSPECTION WITHIN 30 DAYS) | 2/26/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | Car Door restrictor shall work. (less than 4" opening) (REINSPECTION WITHIN 30 DAYS) | 2/26/2021 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm and light shall work with power loss. | 10/22/2021 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.8 Switch Keys | No | No | Hall phase 1 switch shall be FEOK1 and Bezel shall be “reset,off,on” | 10/22/2021 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm and light shall work with power loss. | 10/22/2021 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.8 Switch Keys | No | No | Hall phase 1 switch shall be FEOK1 and Bezel shall be “reset,off,on” | 10/22/2021 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil log &Fire service log, recorded monthly | 9/15/2022 |