Inspection
Inspection Details
Equipment ID
20654
20654
Inspection Date
8/4/2023
8/4/2023
Inspection Type
Alteration
Alteration
Inspector Name
Mitchell McNeely
Mitchell McNeely
Mechanic Name
Jonathan Harrison
Jonathan Harrison
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
150
150
Door Closing Force
Na
Na
External ID
aa5d6a29-50f2-43db-87f5-e0d0489e70d3
aa5d6a29-50f2-43db-87f5-e0d0489e70d3
Location
Stifel Theatre
1400 Market St, St. Louis, MO
Phone: (314) 499-7701
1400 Market St, St. Louis, MO
Phone: (314) 499-7701
Owner
Attn: Adrian Silverstein
Scottrade Center
1401 Clark Ave, St. Louis, MO 63103
Phone: (314) 499-7701
Scottrade Center
1401 Clark Ave, St. Louis, MO 63103
Phone: (314) 499-7701
Billing
Attn: Scottrade Center
Stifel Theatre
1401 Clark Ave, St. Louis, MO 63103
Phone: (314) 499-7701
Email: QReed@StlBlues.com
Stifel Theatre
1401 Clark Ave, St. Louis, MO 63103
Phone: (314) 499-7701
Email: QReed@StlBlues.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Yes | No | Elevator safety drum rope was replaced at some point in time with a non code conforming material. Safety drum rope must be of a corrosion resistant non ferrous material and not of tiller rope construction, needs to be replaced. Re-inspection required | 9/12/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to perform no-load testing of car safeties after safety drum rope is replaced with proper material. Re-inspection required | 9/12/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher in machine room is expired, have serviced or replaced | 10/1/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide testing of the elevator on emergency power. | 10/9/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.12 - Standby power selection switch | 2.27.2 | Yes | No | Provide testing of the elevator emergency power selector switch. Located next door in the security office. | 10/9/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.27 - Crosshead data plate | 2.16.3 | No | No | Provide correct speed on the cross head data plate. | 10/1/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | No | No | Numerous ledges in the hoistway exceed code requirement of 4”, repair as needed. | 10/1/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | Provide pit light to work. | 10/1/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required | 10/1/2025 |
| MO Minimum : Elevators | (K) - Car Platforms and Car Slings | (K)4 | No | No | Install crosshead data plate with correct speed (200 fpm) | 10/1/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Shorten suspension cables to get a minimum of 6" of counterweight runby | 4/10/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required | 4/10/2026 |
| MO Minimum : Elevators | (K) - Car Platforms and Car Slings | (K)4 | No | No | Install crosshead data plate with correct speed (200 fpm) | 4/10/2026 |