Inspection
Inspection Details
Equipment ID
9679
9679
Inspection Date
7/3/2023
7/3/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Don McFadden, Jr.
Don McFadden, Jr.
Relief Valve Pressure
410
410
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
21
21
External ID
24fbc32f-1702-46e2-bb09-2b056d59ff50
24fbc32f-1702-46e2-bb09-2b056d59ff50
Location
675 Medical Office Bldg
675 Old Ballas Rd, Creve Coeur, MO
Phone: (314) 542-0777
675 Old Ballas Rd, Creve Coeur, MO
Phone: (314) 542-0777
Owner
Attn: Tina Moser
Scott Properties
1065 Executive Pkwy Dr, Ste 300, Creve Coeur, MO 63141
Phone: (314) 542-0777
Email: tmoser@scottproperties.com
Scott Properties
1065 Executive Pkwy Dr, Ste 300, Creve Coeur, MO 63141
Phone: (314) 542-0777
Email: tmoser@scottproperties.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 8.11.2.1.3(o) | No | No | Provide numbering of car on cross head. | 10/1/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 8.11.2.1.3(o) | No | No | Provide numbering on inside of car. | 10/1/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.7 Firefighters' Emergency Operation: Operating Procedures | No | No | Post correct Phase 2 operation instructions in car, remove incorrect instructions. | 10/1/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 7/27/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Rollers on selector/switch tree shows excessive wear. Take corrective action as needed. | 8/9/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | Yes | Two-way communication device shall work. Phone line is dead. Unit Red Tagged due to phone and alarm both being inoperative. | 8/13/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | Yes | Alarm bell shall work with loss of main 120v power. Unit Red Tagged due to phone and alarm both being inoperative. | 8/13/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency lighting shall work. | 8/13/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Fire service test log not being properly documented. No logs for 2022 - 2024. | 11/21/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Provide machine room ventilation to meet OEM temperature/humidity requirements. AC unit not working. | 11/21/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | All car call button lamps do not work. | 11/21/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell shall work with loss of main 120v power. | 11/21/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency lighting shall work. | 11/21/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Fire service test log not being properly documented. No logs for 2022 - 2024. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Provide machine room ventilation to meet OEM temperature/humidity requirements. AC unit not working. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | All car call button lamps do not work. |