Inspection
Inspection Details
Equipment ID
12990
12990
Inspection Date
9/29/2017
9/29/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Relief Valve Pressure
490
490
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
Location
Lakeview Medical Center
2 Harbor Bend Ct, Lake St. Louis, MO
Phone: (314) 610-1489
2 Harbor Bend Ct, Lake St. Louis, MO
Phone: (314) 610-1489
Owner
SAM Baiq LLC
#2 Harbor Bend Ct, Suite 202, Lake St. Louis, MO 63367
#2 Harbor Bend Ct, Suite 202, Lake St. Louis, MO 63367
Billing
Attn: SAM Baiq LLC
#2 Harbor Bend Ct, Suite 202, , MO 63367
#2 Harbor Bend Ct, Suite 202, , MO 63367
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | Place current misosuri state operating certificate in elevator machine room | 1/31/2019 | ||
| conversion | conversion | n/a | Repair machine room lights (not working) | 1/31/2019 | ||
| conversion | conversion | n/a | Maintenance has not been done on fire extinguisher in elevator machine room since 2013. Perform maintenance. | 1/31/2019 | ||
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Place current operating certificate in machine room. | 11/28/2023 | ||
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current State certificate in machine room | 11/28/2023 | ||
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | Perform monthly fire service test & document on log in machine room | 11/28/2023 | ||
| A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.11.3.1.2(h) | Remove all non elevator storage from the machine room | 11/28/2023 | ||
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.11.3.1.5(a) | Repair pit light | 11/28/2023 | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | Overspeed valve needs full load test and tripping speed checked before or on the next inspection. | 11/28/2023 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Phone in elevator cab does not work. Phone line or programming issue. | 3/30/2023 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | x | Overspeed valve needs full load test and tripping speed checked before or on next inspection | 10/27/2023 | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current State certificate in machine room. | 11/28/2023 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | Remove all non elevator storage from the machine room. | 11/28/2023 |