Inspection
Inspection Details
Equipment ID
19762
19762
Inspection Date
7/18/2023
7/18/2023
Inspection Type
Alteration
Alteration
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
30/270
30/270
Door Closing Force
NA
NA
External ID
19389e9d-f400-4300-a3a0-9951a6f596d1
19389e9d-f400-4300-a3a0-9951a6f596d1
Location
Bank of Washington
200 W Main St, Washington, MO
Phone: (636) 221-3633
Email: jklak@bankofwashington.com
200 W Main St, Washington, MO
Phone: (636) 221-3633
Email: jklak@bankofwashington.com
Owner
Attn: Bank of Washington
Bank of Washington
PO Box 377, Washington, MO 63090
Phone: (000) 000-0000
Email: jklak@bankofwashington.com
Bank of Washington
PO Box 377, Washington, MO 63090
Phone: (000) 000-0000
Email: jklak@bankofwashington.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 8.6.1.6.2 | Yes | No | Governor sheave will need to be replaced and set safeties on reinspection within 60 days. | 1/19/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work. | 7/23/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication inoperable. Re-inspection required | 9/30/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power, annually. | 9/22/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Fire service must be tested and documented monthly. No Logs for 2022 - 2025. | 9/22/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. No MCP, repair/PM/Callback logs for 2022 - 2025. | 9/22/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/22/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Fire service must be tested and documented monthly. No Logs for 2022 - 2025. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. No MCP, repair/PM/Callback logs for 2022 - 2025. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. |