Inspection
Inspection Details
Equipment ID
5154
5154
Inspection Date
10/3/2017
10/3/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Relief Valve Pressure
340
340
Slide
Governor Rope Pull
Door Closing Force
26/27
26/27
External ID
Location
Maplewood High School
7539 Manchester Rd, Maplewood, MO
Phone: (314) 644-4400
7539 Manchester Rd, Maplewood, MO
Phone: (314) 644-4400
Owner
Maplewood Richmond Hts School Dist
7539 Manchester Rd, St. Louis, MO 63143
7539 Manchester Rd, St. Louis, MO 63143
Billing
Attn: Maplewood-Richmond Hts Schools
7539 Manchester Rd, , MO 63143
7539 Manchester Rd, , MO 63143
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | x | Emergency phone and light not working | 7/23/2018 | |
| conversion | conversion | n/a | Repair drop ceiling panels | 10/14/2025 | ||
| conversion | conversion | n/a | Door open button opens door when elevator goes into floor on Phase I | 10/14/2025 | ||
| conversion | conversion | n/a | Cam does not hit final limit | 10/14/2025 | ||
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | The fire extinguisher in the machine room is expired. A current test, ABC type fire extinguisher shall be provided in the elevator machine room. | 10/14/2025 | ||
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 10/14/2025 | ||
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | The cab lighting shall be guarded. | 10/14/2025 | ||
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 1001.2(a)(12) | Replace the missing ceiling panel. | 10/14/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | x | Electric eye is not working. | 1/31/2025 | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/14/2025 | ||
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | Fire service testing must be properly documented monthly on log sheet. | 10/14/2025 | ||
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/14/2025 |