Inspection
Inspection Details
Equipment ID
17697
17697
Inspection Date
8/10/2023
8/10/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
19
19
External ID
60c67bca-0cbc-47df-90b6-b1a3ea22b73c
60c67bca-0cbc-47df-90b6-b1a3ea22b73c
Location
Delmar Loop Apartments
5621 Delmar Blvd, St. Louis, MO
Phone: (000) 000-0000
5621 Delmar Blvd, St. Louis, MO
Phone: (000) 000-0000
Owner
Attn: Delmar Loop Apartments c/o Unified Residential
Delmar Loop Apartments c/o Unified Residential
10330-DD Lake Rd, Houston, TX 77070
Phone: (000) 000-0000
Email: rmartinez@unified-residential.com
Delmar Loop Apartments c/o Unified Residential
10330-DD Lake Rd, Houston, TX 77070
Phone: (000) 000-0000
Email: rmartinez@unified-residential.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | In car emergency light shall work. | 1/2/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency bell and phone shall work. | 10/16/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The existing machine room air conditioner (window unit) shall be repaired or replaced. | 2/28/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | The photo eyes for the door re-opening device shall be operational. (The mechanical safety edge is operational) | 10/8/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The emergency lighting shall be operational. | 10/8/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | The photo eyes for the door re-opening device shall be operational. (The mechanical safety edge is operational) | 8/26/2021 |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 8.10.2.2.4(b) | Yes | No | The basement floor has an iron gate attached to the door frame. A key is required to open this gate, thus restricting a person from exiting the elevator at that floor. If the elevator was to fall and get stuck at that floor a person or persons would be entrapped. This is a safety hazard, remove the gate. Doors shall not lock any landing opening in the hoistway enclosure from the hoistway side nor lock any exit leading from any hoistway landing to outside of the building. | 11/15/2022 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(d)(1) | Yes | No | Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 11/15/2022 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Yes | No | Post a current MO state operating certificate. | 11/15/2022 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(c)(2) | Yes | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. | 11/15/2022 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 8.10.2.2.2(d) | Yes | No | The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key. | 11/15/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Door restrictor is missing. | 1/19/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | The Phase 1 visual signal shall be operational at the fire service key switch. | 1/19/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove water from pit floor and clean pit. |