Inspection
Inspection Details
Equipment ID
9357
9357
Inspection Date
8/18/2023
8/18/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Healy
David Healy
Mechanic Name
Jessica Lawler
Jessica Lawler
Relief Valve Pressure
588
588
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
24
24
External ID
5a90e629-2226-4eac-8534-8b702767d145
5a90e629-2226-4eac-8534-8b702767d145
Location
The National Golf Club of KC
6700 N National Dr, Parkville, MO
Phone: (816) 746-0200
6700 N National Dr, Parkville, MO
Phone: (816) 746-0200
Owner
Attn: Coby Greenwood
The National Golf Club of KC
PO Box 14146, Parkville, MO 64152
Phone: (000) 000-0000
Email: Coby.Greenwood@clubcorp.com
The National Golf Club of KC
PO Box 14146, Parkville, MO 64152
Phone: (000) 000-0000
Email: Coby.Greenwood@clubcorp.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarmbell not working | 10/30/2018 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Emg. Lt. not working | 9/14/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt. displayed | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | Yes | No | battery lowering not working | 8/5/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | oil an oily rags on pit floor | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | car lights not guarded or sleeved | |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.11.3.1.1(r) | Yes | No | car door locking device not working 8.6.4.13.1(L) | 8/5/2022 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | Yes | No | Repair the battery lowering. | 8/18/2023 |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.19.16 | Yes | No | Repair the door restrictor. | 8/18/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean the pit | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Guard the cab lights. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | non elevator equipment in machine room | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | car lts. need to be guarded | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | pit needs to be cleaned | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | meterials not related to maint or operation of the elev. need to be removed from mach. room | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | battery lowering failed | 8/22/2025 |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.13.1(l)(Door Restrictor) | Yes | No | door restrictor not working | 8/22/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt displayed | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | materials unrelated to elev stored in mach. room | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | car lighting needs to have cover put over box an tubes guarded |