Inspection
Inspection Details
Equipment ID
10177
10177
Inspection Date
9/12/2018
9/12/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
440
440
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
8d48df78-5c97-41ff-9187-c903bfcc1965
8d48df78-5c97-41ff-9187-c903bfcc1965
Location
Hidden Lake Care Center
11750 HIDDEN LAKE DR, SAINT LOUIS, MO
11750 HIDDEN LAKE DR, SAINT LOUIS, MO
Owner
Hidden Lake Care Center
11750 HIDDEN LAKE DR, SAINT LOUIS, MO 63138-1762
11750 HIDDEN LAKE DR, SAINT LOUIS, MO 63138-1762
Billing
Attn: Hidden Lake Care Center
11750 HIDDEN LAKE DR, SAINT LOUIS, MO 63138-1762
11750 HIDDEN LAKE DR, SAINT LOUIS, MO 63138-1762
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate. | 11/21/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The in car emergency telephone shall be operational with 24/7 support. | 11/4/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display a copy of the current state operating certificate. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | No | No | The car top emergency exit shall be properly secured to prevent falling. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | There appears to be a recently installed sprinkler head in the machine room, if this sprinkler head was not existing prior to July 1st, 1999, provide a heat detector within 24" of sprinkler head, provide a shunt trip type breaker located in the machine room, and provide 110v monitoring of shunt trip. | 11/4/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | Evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | The overspeed valve is not sealed and has been previously cited in the past that category 5 testing is due. A category 5 test shall be performed within 90 days. | 3/15/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | The machine room lights shall be guarded. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 3/15/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.5 Code Data Plate | No | No | The code data plate required by A17.1 2016 8.9 shall be provided in plain view, securely attached to each main line disconnect or controller. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | The data on the MCP shall be filled out as required by A17.1 2016 8.6.1.4.1(a)(3). | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | Yes | No | The car-top emergency exit shall be secured to prevent it from falling down the hoistway. (2nd Notice) Re-inspection required. | 3/15/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | No | No | Top of car emergency exit is secured, but shall have a chain or means to keep from falling down hoistway if removed. |