Inspection
Inspection Details
Equipment ID
20650
20650
Inspection Date
8/9/2023
8/9/2023
Inspection Type
Alteration
Alteration
Inspector Name
Michael Bailey
Michael Bailey
Mechanic Name
Jonathan Harrison
Jonathan Harrison
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
140/
140/
Door Closing Force
na
na
External ID
b16d99e0-160b-42c9-962a-b82a558ed6b5
b16d99e0-160b-42c9-962a-b82a558ed6b5
Location
Stifel Theatre
1400 Market St, St. Louis, MO
Phone: (314) 499-7701
1400 Market St, St. Louis, MO
Phone: (314) 499-7701
Owner
Attn: Adrian Silverstein
Scottrade Center
1401 Clark Ave, St. Louis, MO 63103
Phone: (314) 499-7701
Scottrade Center
1401 Clark Ave, St. Louis, MO 63103
Phone: (314) 499-7701
Billing
Attn: Scottrade Center
Stifel Theatre
1401 Clark Ave, St. Louis, MO 63103
Phone: (314) 499-7701
Email: QReed@StlBlues.com
Stifel Theatre
1401 Clark Ave, St. Louis, MO 63103
Phone: (314) 499-7701
Email: QReed@StlBlues.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Fire extinguisher in machine room is expired. Replace or have serviced | 10/1/2025 | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Car safeties need to be tested after safety drum rope is replaced. Re-inspection required | 9/13/2023 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | x | Elevator safety drum rope was replaced at some point in time with a non code conforming material. Safety drum rope must be of a corrosion resistant non ferrous material and not of tiller rope construction. Re-inspection required | 9/13/2023 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Provide testing of the elevator on emergency power. | 10/8/2024 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.12 - Standby power selection switch | 2.27.2 | x | Provide testing of the elevator emergency power selector switch, located next door in the security office. | 10/8/2024 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.7 Firefighters' Emergency Operation: Operating Procedures | Post Phase I instructions near the f/f switch in the lobby. | 10/1/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | Observed numerous ledges exceeding 4”code requirement, repair as needed. | 10/1/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.27 - Crosshead data plate | 2.16.3 | Provide correct car speed on the cross head data plate. | 10/1/2025 | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Need to test elevator for operation on emergency power. Re-inspection required | 10/1/2025 | |
| MO Minimum : Elevators | (K) - Car Platforms and Car Slings | (K)4 | Install crosshead data plate with correct speed (200 fpm) | 10/1/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | Shorten suspension cables to get a minimum of 6" counterweight runby | |||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Need to test elevator for operation on emergency power. Re-inspection required | ||
| MO Minimum : Elevators | (K) - Car Platforms and Car Slings | (K)4 | Install crosshead data plate with correct speed (200 fpm) |