Inspection
Inspection Details
Equipment ID
18397
18397
Inspection Date
8/21/2023
8/21/2023
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Thomas Jimas
Thomas Jimas
Relief Valve Pressure
Na
Na
Slide
11”
11”
Governor Rope Pull
35/200
35/200
Door Closing Force
25/26
25/26
External ID
f9b583c9-3433-4325-81b4-45a0f28ebaf4
f9b583c9-3433-4325-81b4-45a0f28ebaf4
Location
Ely Walker Lofts
1520 Washington Ave, St. Louis, MO
Phone: (314) 591-9715
1520 Washington Ave, St. Louis, MO
Phone: (314) 591-9715
Owner
Attn: Ely Walker Condo Assoc.
Ely Walker Condo Assoc.
1520 Washington Ave, St. Louis, MO 63103
Phone: (000) 000-0000
Email: bobbie@cpmgateway.com
Ely Walker Condo Assoc.
1520 Washington Ave, St. Louis, MO 63103
Phone: (000) 000-0000
Email: bobbie@cpmgateway.com
Billing
Attn: Ely Walker Condo
Ely Walker Condo c/o Sentry Management
9666 Olive Blvd, Ste 116, St. Louis, MO 63132
Phone: (314) 994-7440 Ext: 57500
Email: AJohnson@smithmgmt.com
Ely Walker Condo c/o Sentry Management
9666 Olive Blvd, Ste 116, St. Louis, MO 63132
Phone: (314) 994-7440 Ext: 57500
Email: AJohnson@smithmgmt.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | camera wiring on car top trip hazard | 5/1/2020 |
| conversion | conversion | n/a | No | No | need capacity plate in car | 5/1/2020 |
| conversion | conversion | n/a | No | No | Copy of permit to be on display in elevator equip room | 5/1/2020 |
| conversion | conversion | n/a | No | No | Replace protective cover on beams at first floor for travel cable | 5/1/2020 |
| A17.1-1996 : Elevators | 1.3 - Operating control devices | 1001.2(a)(3) | No | No | Door open inoperative on attendant service operation. Repair | 5/1/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)12 | Yes | No | Phase II inoperative. Repair. | 7/28/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The signage for “In Case of Fire Use Stairs” is not located on all landings.. Install signage that conforms to the building code this elevator was installed to meet. | 1/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.12 - Controller Wiring, Fuses, Grounding, Etc. | 8.6.1.6.1 | No | No | The emergency rescue battery in the controller shall be changed. The Manufacture’s written procedure is for replacement every 3 years. If the battery becomes depleted the elevator will automatically stop operating. Replace the battery of this elevator before it shuts down due to battery being depleted. | 1/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. | 1/1/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The fireman’s emergency service phase II instruction signage adjacent to the keyed switch in the car is unreadable and shall be replaced.. | 1/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | No | No | A temporary construction barrier was installed in the elevator hoistway between the elevator cars. This barrier is designed for only temporary use and shall be removed from the hoistway. | 1/1/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The fireman phone jack on the car operating panel in the car is pushed in resulting in a possible electrical hazard and shall be repaired. | 1/1/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | No | No | The car flooring tile is missing at a number of locations resulting in a potential tripping hazard to passengers. Repair the flooring to minimize the risk of of the tripping hazard. | 1/1/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The car directional arrows on the left side has been damaged and removed. Replace directional arrow as required. | 1/1/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 9/9/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Need to replace illegible bezels for car operating panel buttons: Car Cancel & phone | 9/9/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.2 - Car top light and outlet | 2.14.7 | No | No | Repair / replace nonworking cartop light switch and rear light | 9/9/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit has standing water, remove water and repair / replace sump pump | 9/9/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need to remove debris from pit | 9/9/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | Need to clean car top | 9/9/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for elevator controller | 9/9/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit has standing water. Remove water and repair/replace sump pump | 9/9/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The car directional arrows on the left side has been damaged and removed. Replace directional arrow as required | 9/9/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.7 Cleaning of Hoistways and Pits | No | No | Standing water in pit. Pit shall be kept clean and dry and sump shall be repaired. |